background image

www.trioniaq.com

Grease Viper

13

I n s t a l l a t i o n ,   O p e r a t i o n ,   a n d   S e r v i c e   M a n u a l

•  If the short is in the collector section, look 

for a large piece of foreign material bridging 

the collector plates or a defective insulator.

•  If the short is indicated to be in both 

sections, it will probably be a foreign object 

bridging the air gap between the ionizer and 

the collector.

c. Open Circuits: Although open circuits can 

occur in the secondary, they usually take place 

in the primary. If the unit contains only one 

power supply and the indicating light does not 

glow the outage is probably one of the following:

•  Supply line power to the control 

disconnected. Reconnect.

•  Open access door interlock in control of 

electronic air cleaner. Be sure all access 

doors are properly closed and secured.

•  Blown in-line fuse located on the transformer. 

Identify short and replace fuse.

•  Outage in the power supply. Look for 

charred or burned components or a loose 

wiring connection. Replace power supply or 

reconnect wiring.

•  Defective indicating light. Replace light.

d.  Malfunctions other than short or open circuits 

- refer to the Troubleshooting Reference Chart 

below.

Problem/Symptom Probable Cause

Location

Reason - Correction

Indicating Light 

Not Glowing

Short Circuit

Ionizing Section of Cell

1.  Dirty Insulator(s) - Clean

2.  Defective Insulator(s) - Replace

3.  Foreign Object between Spiked Ionizer and Ground 

Electrode - Remove

Collecting Section of Cell

1.  Dirty Insulator(s) - Clean

2.  Defective Insulator(s) - Replace

3.  Foreign Material Bridging Plates - Remove

4.  Bent Plates - Straighten or Replace Cell

Power Supply

Charred/Overheated Components - Replace Power Supply

Indicating Light 

Not Glowing

Open Circuit

Control

Transformer - Check 24 VAC Input

Power Supply

1.  Disconnected Wire - Reconnect

2.  Charred/Overheated Components - Replace Power 

Supply

Electrostatic Precipitator 

Housing

1.  Electrical Interlock Switch Not Closed - Close Ac-

cess Door

2.  Faulty Electrical Interlock Switch - Replace

LED

1.  Incorrect Polarity - Correct Wiring

2.  Faulty LED - Replace LED

Indicating Light 

Flickering

High Resistance 

Short

High Voltage Circuit

1.  Loose or Defective Inter-cell Connection (on Multi-

cell Units) - Tighten or Replace

2.  Foreign Object Adrift in Ionizer or Plate Section of 

Cell - Remove

Содержание Grease Viper Series

Страница 1: ...T R I O N w w w t r i o n i a q c o m Grease Viper Series Electrostatic Precipitators Commercial Industrial Applications READ AND SAVE THESE INSTRUCTIONS ...

Страница 2: ...or 1 Unpack and Inspect 4 2 Position Air Cleaner Cabinet 5 3 Connect Adjoining Ductwork 5 4 MountDetergentSystem 5 5 Connect Drain 5 6 Connect Water Wash Supply 5 7 MountControlPanel 6 8 Complete Wiring a Primary Wiring 6 b Grounding 6 9 Checkout for System Start up 6 Section 3 Operation Service For the Maintenance Engineer 1 Introduction and Principle of Operation 6 2 General Description 7 3 Init...

Страница 3: ...reactivated carbon Gasketed access doors located on one side of the cabinet 90 degrees to the direction of the airflow provide entry for removal of the cells and filters The location of the access doors may be specified as right hand or left hand access determined by facing the inlet of the ESP dirty airflow at your back The solid state high voltage power supplies are factory installed and wired w...

Страница 4: ...nit and detergent system Where applicable all water lines must be protected from freezing SAFETY NOTE Factory designed access to all electrically charged high voltage components contain electrical interlocks for the safety of operating personnel Any additional access that may be provided in the system where there is access to high voltage must be equipped with such interlocks Interlocks are readil...

Страница 5: ... pan supply through the floor The recommended drain line trap to seal off the cabinet from the drain against the system pressure and the drain dump valve should be located in the heated interior If not installed in this manner heat trace or other means should be employed to prevent freezing Clean outs are recommended to be installed in all drain lines Wash Water Supply Line The length of the wash ...

Страница 6: ...emperatures must be considered see detailed Warning on Page 6 cabinet then re install the ionizing collecting cells and all other filters When the ionizing collecting cells are reinstalled the directional arrows on the cell end plates must concur with airflow direction through the cabinet Impinger prefilters are to be installed within the inlet plenum section on the air entering side of the unit 4...

Страница 7: ...n accordance with the plumbing schematic to prevent freezing 2 All piping exposed to cold climate outdoor conditions should be heat traced and insulated to prevent freezing 3 An air gap fitting should be installed on the drain line to facilitate gravity draining of wash water from the internal headers and manifolds 4 The water supply line should be pitched back toward the heated space 9 Check Out ...

Страница 8: ...s On multi cell units all of the electrical connections between cells in a given tier are automatically made through spring plunger connectors Install cells into the cabinet in accordance with the directional arrows on the cell end plates The side of the cell containing the spiked ionizer blades must always be located on the air entering side The spring plunger connectors located on one end of eac...

Страница 9: ...in the drain basin for any restrictions The ducting where secured to the cabinet collars should be sealed water tight either with gasketing or caulking 2 Inspect the ionizing collecting cells to see that all of the ionizing blades are intact that no large pieces of foreign material are lodged between the plates and that the cells are properly installed in the cabinet with the spiked ionizing blade...

Страница 10: ...ion is only effective when timer is running in AUTO mode Temporary Override Condition 1 When timer s output status is ON press MANUAL key to move indicator from AUTO to OFF Timer output shall turn to OFF status programs overrided Press MANUAL again to switch timer status to AUTO Timer s output shall continue maintaining OFF Timer shall resume its automatic operation when next program event calls f...

Страница 11: ...he inside of the tank should be kept clean free from dirt and foreign objects The detergent as supplied by TRION is formulated specifically for electronic air cleaners If substitutes are used they must be approved by TRION so as to not void the warranty They should be safe for use in ventilation systems and non caustic as 95 of the ionizing collecting cells are constructed of aluminum special high...

Страница 12: ... or cleaning shall be maintained on the premises WARNING RISK OF ELECTRIC SHOCK These servicing instructions are for use by qualified personnel only To reduce the risk of electric shock do not perform any servicing other than that contained in the operating instructions unless you are qualified to do so NOTE All repairs to the fire suppression system if supplied must be completed by the authorized...

Страница 13: ...h voltage power supply s is 12 000 VDC and up to 8 MA When the power supply s is de energized there is a 20 second delay for the voltage to decay Always short from ground to a point of high voltage with a well insulated jumper wire or an insulated handled screwdriver to bleed off any remaining residual charge NOTE It will be necessary to close the access door electrical interlock switch operated b...

Страница 14: ... indicating light Replace light d Malfunctions other than short or open circuits refer to the Troubleshooting Reference Chart below Problem Symptom Probable Cause Location Reason Correction Indicating Light Not Glowing Short Circuit Ionizing Section of Cell 1 Dirty Insulator s Clean 2 Defective Insulator s Replace 3 Foreign Object between Spiked Ionizer and Ground Electrode Remove Collecting Secti...

Страница 15: ...on and Buyer s sole and exclusive remedy for any breach of this warranty repair or replace reperform the Goods which gave rise to the breach or at Seller option refund the amounts paid by Buyer for the Goods which gave rise to the breach Any repair replacement or reperformance by Seller hereunder shall not extend the applicable Warranty Period The parties shall mutually agree on the specifications...

Страница 16: ...TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com TRION 2017 All Rights Reserved Form No 266206 001 Rev 09 17 ...

Отзывы: