www.trioniaq.com
Grease Viper
13
I n s t a l l a t i o n , O p e r a t i o n , a n d S e r v i c e M a n u a l
• If the short is in the collector section, look
for a large piece of foreign material bridging
the collector plates or a defective insulator.
• If the short is indicated to be in both
sections, it will probably be a foreign object
bridging the air gap between the ionizer and
the collector.
c. Open Circuits: Although open circuits can
occur in the secondary, they usually take place
in the primary. If the unit contains only one
power supply and the indicating light does not
glow the outage is probably one of the following:
• Supply line power to the control
disconnected. Reconnect.
• Open access door interlock in control of
electronic air cleaner. Be sure all access
doors are properly closed and secured.
• Blown in-line fuse located on the transformer.
Identify short and replace fuse.
• Outage in the power supply. Look for
charred or burned components or a loose
wiring connection. Replace power supply or
reconnect wiring.
• Defective indicating light. Replace light.
d. Malfunctions other than short or open circuits
- refer to the Troubleshooting Reference Chart
below.
Problem/Symptom Probable Cause
Location
Reason - Correction
Indicating Light
Not Glowing
Short Circuit
Ionizing Section of Cell
1. Dirty Insulator(s) - Clean
2. Defective Insulator(s) - Replace
3. Foreign Object between Spiked Ionizer and Ground
Electrode - Remove
Collecting Section of Cell
1. Dirty Insulator(s) - Clean
2. Defective Insulator(s) - Replace
3. Foreign Material Bridging Plates - Remove
4. Bent Plates - Straighten or Replace Cell
Power Supply
Charred/Overheated Components - Replace Power Supply
Indicating Light
Not Glowing
Open Circuit
Control
Transformer - Check 24 VAC Input
Power Supply
1. Disconnected Wire - Reconnect
2. Charred/Overheated Components - Replace Power
Supply
Electrostatic Precipitator
Housing
1. Electrical Interlock Switch Not Closed - Close Ac-
cess Door
2. Faulty Electrical Interlock Switch - Replace
LED
1. Incorrect Polarity - Correct Wiring
2. Faulty LED - Replace LED
Indicating Light
Flickering
High Resistance
Short
High Voltage Circuit
1. Loose or Defective Inter-cell Connection (on Multi-
cell Units) - Tighten or Replace
2. Foreign Object Adrift in Ionizer or Plate Section of
Cell - Remove