NOTICE.
Use suitable devices for
connecting the luminaire. A suitable
device is e.g. a cable junction box
with series terminals for cables with
cross-section X x 1,5
□
/ 2,5
□
/ and
rated voltage of 250/400V.
On customer request, connecting
cables with additional wires can be
used. Protect the unused wires from
contact on site.
EN
EN
For your safety
Read all instructions and mounting steps
carefully. Keep the instructions for maintenance
or disassembly work.
Explanation of the warning levels
Observe and follow the warnings.
Non-observance of the warnings may lead
to injuries or material damage!
WARNING!
Indicates dangers which
can result in serious and/or fatal
injuries.
CAUTION!
Indicates dangers which
can result in injuries or health hazards.
NOTICE.
Indicates dangers which
can result in material damage or
malfunctions.
TIP.
Indicates information containing
advice or a useful note.
Explanation of important symbols and
pictograms
Indicates professional personnel who
are trained and authorised to carry out
the electrical connection.
Indicates professional personnel who
are trained and authorised to carry
out the mounting.
Safety notes
WARNING!
Risk of electric shock!
Never work with voltage applied.
WARNING!
Risk of electric shock!
The light source of this luminaire shall
only be replaced by the manufacturer
or a service technician authorised by
the manufacturer or a similar
qualified person. If the light source
malfunctions or fails, please contact
TRILUX.
CAUTION!
Risk of eye damage! Do not
stare into the active light source.
LED module: risk group 2. Position the
luminaire so that looking for a longer
period of time into the luminaire at
a distance closer than 0.4 m is not
expected.
NOTICE.
Wear clean installation
gloves to prevent soiling.
Important information on electronic control
gear units (ECG)
A neutral conductor interruption in the three-
phase circuit leads to overvoltage damage in the
lighting system. Only open the neutral conduc-
tor isolating terminal in de-energised state, and
close the neutral conductor isolating terminal
before switching on again. Do not exceed the
maximum permissible ambient temperature ta
of the luminaire.
Exceeding this limit reduces the service life
and in extreme cases there is a risk of premature
failure of the luminaire. Design connection
cables for the control inputs of DALI control
gear (1-10 V, DALI etc.) to be 230 V mains volt-
age-proof (basic insulation).
Intended use
Intended for outdoor use with a maximum
ambient temperature of:
ta 35 °C
Safety class:
II
Protection rating:
IP65
Disposal of waste electrical and electronic
equipment
Always collect and dispose of old elec-
trical and electronic equipment sep-
arately at the end of its service life. In
case of doubt, seek information about environ-
mentally-compliant waste disposal from your
local district authority or special waste dis-
posal companies. Current information on the
energy efficiency class of the selected product
version can be found in the corresponding data
sheet for the luminaire. Instructions for replac-
ing or removing the light source in accordance
with Regulation 2019/2020/EU can be found at:
www.trilux.com/EcoDesign
Important information on load effects.
The luminaire meets the requirements of
IEC 60598 and is designed for the exposure to
wind according to EN 1991 (Eurocode) with
basic velocity of up to 30 m/s (corresponds
to wind zone 4 in Germany) in terrain category 1.
A snow load (up to 1 kN/m²) and icing (up to
20 mm) at a mounting height according to the
mounting instructions are taken into account.
Impact loads and exposed locations such as
bridges, installation on buildings and in
stallation directly adjacent to railway tracks
are not taken into account.
Important information on the connecting cable.
Operate the luminaire only with an
undamaged outer cable. To avoid hazards,
a damaged outer cable of this luminaire
shall only be replaced by TRILUX, its service
partner or a comparably qualified person.
Important information on mounting the
luminaire
With LED outdoor luminaires with safety
class II, weather-induced static charges in the
luminaire housing may impair the function
and service life of the LED modules. TRILUX
recommends: Mount the luminaire in such a
way that there is a low-resistance electrical
connection from the luminaire housing to the
ground.
Directive 2014/53/EU
Simplified EU Declaration of Conformity
according to the RED Directive if the luminaire
is equipped with a control gear unit with NFC
interface or a radio component:
TRILUX hereby declares that the following
radio system type complies with Directive
2014/53/EU:
The full text of the EU Declaration of Confor-
mity is available on the Internet at:
www.trilux.com/eu-conformity
CS
...
TIP.
TRILUX recommends 2-person
installation.