background image

Product manual EM converterLED ST | 08-2018 | 1.0 | en

Settings for emergency tests

c

20 / 38

6.1. Test times and test intervals

Devices of the EM converterLED ST series are tested via selftest function. The following table gives an overview of the parameters:

Test trigger

Test times

Test intervals

Test
triggered by
emergency
lighting unit

There are two variants for setting the test time. In some cases different rules apply for the
setting of the day and the time:

To prevent that the emergency lighting tests of all luminaires are carried out at the same time,
each luminaire has a pre-programmed code which delays the test time for a specified time (see 

).

Commissioning test

, p. 20

Test time intervals
between the tests
are fixed:

6.2. Commissioning test

The commissioning test is a first duration test. The relevant standard (IEC 62034: Automatic test systems for battery powered
emergency escape lighting) requires that such a test is carried out after the installation.

The commissioning test is often made more difficult because the power supply is switched on and off during the installation phase.
This is the case, for example, if the site is powered off at night for security reasons. To address this problem, the EM converterLED ST
monitors the power supply and will only start with the commissioning test if the power supply hasn't been interrupted for 5 days.

To prevent that all the luminaires perform the emergency test at the same time, each luminaire has a pre-programmed code with a
value of 1-28, which delays the test time of that luminaire for a specified time.

28 days after the start of the commissioning all devices will have completed the required commissioning test.

The day of the commissioning test serves as a reference point for all further function and duration tests (see 

Test times and test

Automatic setting of the function test:
The time of the function test is the same as the time when the device was first
connected to the power supply (see (1) in above diagram), the day of the function test
is the same as the day when the commissioning test was carried out (see (5) in above
diagram and 

).

Commissioning test

, p. 20

_

Automatic setting of the duration test:
The time of the duration test is set by the 

, the day of the

Adaptive test mode

, p. 22

duration test is the same as the day when the commissioning test was carried out (see
(5)  in above diagram and 

).

 

Commissioning test

, p. 20

_

Manual setting of the test time and the test day for a single luminaire via test switch
(see 

).

Setting the test time for one luminaire

, p. 23

_

Manual setting of the test time and the test day for all the luminaires in an emergency
lighting circuit by switching the power supply on and off (see 

Setting the test time for

).

all the luminaires in an emergency lighting circuit

, p. 23

_

Function test:
weekly

_

Duration test:
annual

_

Devices with code 1 will be tested one day after the completion of the 5 day long monitoring of the power supply (that is 6
days after the uninterrupted connection to the supply).

_

Devices with code 2 will be tested two days after the completion of the 5 day long monitoring of the power supply (that is 7
days after the uninterrupted connection to the supply).

_

Devices with higher code numbers will be tested with a delay that corresponds to that code number.

_

Содержание EM converterLED ST

Страница 1: ...8 2 1 7 5 3 4 1 8 3 3 4 2 0 9 ø 4 5 3 3 8 2 1 7 5 5 1 7 3 4 1 8 3 8 2 3 4 2 0 9 1 7 5 3 4 1 8 3 ø 4 5 4 1 8 2 3 4 2 0 9 1 7 5 5 1 7 5 3 4 1 8 3 ø 4 5 3 3 8 2 3 4 2 0 9 LED Driver EM converterLED ST Product Manual ...

Страница 2: ...ustable output current 10 Intelligent multilevel charging system 13 Rest mode Inhibit mode and Relight command 14 Indicator LED 17 Settings for Emergency tests 19 Test times and test intervals 20 Commissioning test 20 Weekly function test 21 Annual duration test 22 Adaptive test mode 22 Functionality of the test switch 22 Determining light output in emergency operation 24 Parameter 1 LED forward v...

Страница 3: ...roduct manual EM converterLED ST 08 2018 1 0 en Table of Contents c 3 38 Installation notes 35 Safety information 35 Routing the wires 36 Reference list 38 Related documents 38 Additional information 38 ...

Страница 4: ...be changes in shape features and technology Claims can therefore not be made on the basis of information diagrams or descriptions in these instructions The latest version of these operating instructions is available on our home page at http www tridonic com com en operating instructions asp 1 2 Copyright This documentation may not be changed expanded copied or passed to third parties without the p...

Страница 5: ...y supplied emergency lighting The device may only be used for this intended purpose 2 1 2 Improper use Outdoor use Extensions and modifications to the product 2 2 Dangers associated with the operation of the system 2 3 Environment WARNING Improper use could result in injury malfunction or damage to property It must be ensured that the operator informs every user of existing hazards DANGER Danger o...

Страница 6: ...2 4 Additional instructions CAUTION Electromagnetic compatibility EMC Although the device meets the stringent requirements of the appropriate directives and standards on electromagnetic compatibility it could potentially interfere with other devices under certain circumstances ...

Страница 7: ... selftest version ST of the portfolio The PRO version is covered in a separate documentation see Reference list p 38 3 2 Testing of emergency systems There are statutory requirements covering the testing of emergency systems in buildings accessible to the public This includes that testing must be carried out at a time of minimum risk normally during unsocial hours and must allow time for the batte...

Страница 8: ... in a low profile housing 21mm Image Description Housing variant compact 4 2 Forward voltage The EM converterLED ST is available with three different forward voltages 10 52 V 40 97 V 50 200 V Compact shape _ For installations inside the luminaire _ Typical area of application Spotlights downlights _ Dimensions 179 30 21 mm _ ...

Страница 9: ...Function test interval weekly Duration test interval annual Rated duration Adjustable to 1 or 2 hours Status display Via two colour indicator LED p 17 Battery charge system Intelligent multilevel charging system p 13 Intermittent charging pulse charging for NiMH batteries Adjustment of output current p 10 Automatic adjustment by device Commissioning Automatic Rest mode Inhibit mode and Relight com...

Страница 10: ...ower ensures maximum light output in emergency mode for the specified operating time An EM converterLED ST with approx 3 4 or 5 watts output power operates the connected LED modules with the output power mentioned before For this purpose the device detects the connected LED forward voltage and adjusts the LED forward current to the appropriate value resulting in an output power of approx 3 4 or 5 ...

Страница 11: ...ange SELV Number of battery cells EM converterLED ST 103 50V 10 52 V SELV 60 V 3 cells for light output in emergency operation EM converterLED ST 103 NiMH 50V 10 52 V SELV 60 V 3 cells for light output in emergency operation EM converterLED ST 104 50V 10 52 V SELV 60 V 4 cells for light output in emergency operation EM converterLED ST 104 50V NiMH 10 52 V SELV 60 V 4 cells for light output in emer...

Страница 12: ...t in emergency operation EM converterLED ST 104 50V 50 200 V no 4 cells for light output in emergency operation EM converterLED ST 104 50V NiMH 50 200 V no 4 cells for light output in emergency operation EM converterLED ST 105 50V 50 200 V no 5 cells for light output in emergency operation EM converterLED ST 105 50V NiMH 50 200 V no 5 cells for light output in emergency operation I NOTICE There is...

Страница 13: ...with an operating time of 1 hour and 15 hours for modules with an operating time of 2 and 3 hours Once the batteries are fully charged again the module automatically switches to trickle charge mode In trickle charge mode the battery status is continually monitored to ensure that the charging currents and battery voltages remain within the specified limits The status LED also shows such faults loca...

Страница 14: ... different changes activating Rest mode and Inhibit mode and sending the Relight command DC voltage pulses of different lengths are used The table at gives an overview of all the operating modes Switching between operating modes p 16 5 3 1 Activate Rest mode Rest mode is activated as follows 5 3 2 Deactivate Rest mode via Relight command By sending the Relight command the Rest mode is deactivated ...

Страница 15: ...se at the two terminal points REST L and REST N _ The signal of must have an amplitude 9 5 22 5 V with a pulse length of 1 001 2 000 ms _ The polarity of the voltage pulse does not matter _ I NOTICE Reapplying the power supply does also deactivate Rest mode In this case the device switches from Rest mode to charge mode Make sure that the mains supply is switched on _ Apply DC voltage pulse at the ...

Страница 16: ... the device switches between these operating modes The following table gives an overview Applied pulse length Charging mode Emergency mode Rest mode Inhibit mode 150 1 000 ms Switches to Inhibit mode Switches to Rest mode 1 001 2 000 ms Relight command Switches to Emergency mode Switches to charging mode Apply DC voltage pulse at the two terminal points REST L and REST N _ The signal of must have ...

Страница 17: ...ally reset Permanent RED Lamp failure Open circuit or Short circuit or LED failure Fast flashing RED 0 1 s on 0 1 s off Charging failure Incorrect charging current I NOTICE After an exchange of the LED module the indicator LED remains permanent RED The lamp failure indication remains set until a function test has been successfully completed automatically with the weekly function test or immediatel...

Страница 18: ...icator LED is slow flashing RED After an exchange of the battery the indicator LED switches to GREEN To guarantee a satisfactory operating time the battery is then charged for 20 hours and a second duration test is carried out I NOTICE Battery is defect or incorrect battery voltage While the battery is in trickle charge mode and the mains supply is connected the micro controller in the emergency u...

Страница 19: ...n to the power supply 2 Phase in which the power supply is switched on and off possibly numerous times 3 Phase in which the power supply is permanently connected no interruption for at least 5 days 4 Delaying the commissioning test for 1 28 day 5 Commissioning test begins 6 First function test 7 First duration test ...

Страница 20: ...uminaire for a specified time 28 days after the start of the commissioning all devices will have completed the required commissioning test The day of the commissioning test serves as a reference point for all further function and duration tests see Test times and test Automatic setting of the function test The time of the function test is the same as the time when the device was first connected to...

Страница 21: ...witched off which can take up to 24 hours the indicator LED shows that the test has not been carried out satisfactorily fast blinking GREEN If the function test detects a battery failure and the battery was not fully charged at the test time the device returns to charging mode and starts the function test a second time once the battery is fully charged _ I NOTICE In this case battery failure and b...

Страница 22: ...ter the duration test before the room is in use again Room usage is monitored on a monthly basis and the time for the duration test is constantly adjusted This allows for seasonality in room usage to be taken into account If a suitable time cannot be found perhaps because the room is in use round the clock the duration test is performed at the time set during startup this is the time when the emer...

Страница 23: ... indicator LED _ A longer press on the button 1 10 s switches the light source to emergency mode but does not perform a time controlled function test On release of the button the emergency units switch back to charge mode The indicator LED goes off for 1 second and then on for the rest of the time maximum of 9 seconds _ I NOTICE Resetting the timer deactivates the Because of this the test time is ...

Страница 24: ... Parameter 1 LED forward voltage 7 1 1 Total forward voltage of all LED modules The forward voltage of a single LED module can be found in the data sheet When calculating the total forward voltage of all LED modules series and parallel circuits must be handled differently Series circuit Parallel circuit The values of the individual LED modules are summed up The total value is the same as the value...

Страница 25: ...ency operation c 25 38 7 1 2 Example 1 1 LED module DLE Given Wanted Result Forward voltage DLE taken from data sheet 24 2 V _ Total forward voltage of all LED modules in emergency operation _ The total forward voltage of all LED modules is because there is only 1 LED module 24 2 V _ ...

Страница 26: ...Given Wanted Result Forward voltage DLE taken from data sheet 24 2 V _ Total forward voltage of all LED modules _ The total forward voltage of all LED modules is V no addition of the values in a parallel circuit 24 2 _ I NOTICE As Example 2 shows parallel circuits make it possible to use multiple LED modules where the forward voltage does not add up ...

Страница 27: ...on c 27 38 7 2 Parameter 2 LED current Each EM converterLED ST has a specific current voltage characteristic The corresponding current voltage curve can be found in the datasheet EM converterLED ST 103 50V EM converterLED ST 103 NiMH 50V EM converterLED ST 104 50V EM converterLED ST 104 NiMH 50V ...

Страница 28: ...Product manual EM converterLED ST 08 2018 1 0 en Determining light output in emergency operation c 28 38 EM converterLED ST 134 NiCd 50V EM converterLED ST 104 90V EM converterLED ST 104 NiMH 90V ...

Страница 29: ...ual EM converterLED ST 08 2018 1 0 en Determining light output in emergency operation c 29 38 EM converterLED ST 105 90V EM converterLED ST 105 NiMH 90V EM converterLED ST 104 200V EM converterLED ST 104 NiMH 200V ...

Страница 30: ...battery voltage and max battery discharge current Knowing the total forward voltage of all LED modules the value for the LED current can be read from the current voltage curve The value of the LED current lies within this range The effective value depends on tolerances Mark the value of the total forward voltage of all LED modules on the x axis of the graph _ From that point move up vertically The...

Страница 31: ...module DLE Given Wanted Result Figure Determining LED current for EM converterLED ST 103 50V Total forward voltage of all LED modules 24 2 V calculated before _ LED current _ The two crossing points are at around 85 mA minimum value and 111 mA maximum value _ The effective value of the LED current is between these two values _ ...

Страница 32: ...rgency operation approx 85 mA minimum value and approx 111 mA maximum value taken from the previous example see Example 1 1 LED module DLE p 31 _ LED current in mains operation 750 mA taken from data sheet DLE G3 2000 lm Article number 89600574 _ Light output in mains operation 2 100 lm taken from data sheet DLE G3 2000 lm Article number 89600574 _ Light output in emergency operation _ Minimum lig...

Страница 33: ...mportant to check that the rating of the LED Driver does not exceed the values specified below 8 3 Practical tests Practical tests are used to ensure fault free operation of the LED module and LED Driver The following aspects must be checked 8 3 1 Technical aspects 8 3 2 Visual aspects EM converterLED ST 50V 10 52 V _ EM converterLED ST 90V 40 97 V _ EM converterLED ST 200V 50 200 V _ Max allowed ...

Страница 34: ...lowing conditions must be considered All tolerances _ Entire temperature range _ Different output voltage ranges incl no load _ Entire dimming range _ Short circuit _ I NOTICE If the values are slightly over or under the specified threshold values or if there are any other concerns or questions please contact Technical Support techservice tridonic com ...

Страница 35: ...ons of the lamp manufacturer _ Observe all relevant standards Follow the instructions given in the standards _ WARNING Comply with the general safety instructions see Safety instructions p 5 _ To avoid failures due to ground faults protect the wiring against mechanical loads from sharp edged metal parts e g cable penetrations cable holders metal frames etc _ Electronic control gear from Tridonic a...

Страница 36: ...rol gear with U 250 V out out For U 480 V the voltage for the type test is 2000 V out 9 2 4 Wiring Wiring guidelines I NOTICE The performance of the prescribed tests and compliance with relevant standards are the responsibility of the luminaire manufacturer The following descriptions merely indicate the most important tests and are no substitute for a full research of the relevant standards CAUTIO...

Страница 37: ...iring the plug in terminal Release of the wiring Use solid wire with the correct cross section _ Strip off correct length of insulation you may need to twist the tool slightly _ Insert the bare end into the terminal _ Press down the push button and remove the cable from front _ ...

Страница 38: ...terLED https www tridonic com com en download technical EM_converterLED_Product description_en pdf _ Brochure Emergency Lighting http www tridonic com com en download Emergency_Lighting_Overview_EN pdf _ EM converterLED current calculator https www tridonic com com en products converterled _ Data sheets http www tridonic com com en data sheets asp _ Company certificates http www tridonic com com e...

Отзывы: