PRESTIGE Venturi

Replacement Kit 

3

For the reassembly process do not use adhe-
sive on any gasket surface.

11.  Install  the  venturi  gasket  on  the  venturi  and

reassemble the venturi / gas valve assembly to
the  blower  housing  using  the  (2)  M5  x  12
mounting  screws  supplied  in  the  kit.    Use  the
#25  Torx  wrench  to  tighten  all  screws  and
secure the assembly.

12. Reconnect  the  rectifier  plug  to  the  gas  valve

using the Phillips head screw (MCBA).

13. Reconnect  Molex  plug  to  the  gas  valve

(TriMax).

14.  Reconnect  the  brass  gas  piping  union  connec-

tion. Open the  main manual gas shutoff valve
before  placing  the  PRESTIGE  unit  back  into
operation check and test all gas connections for
leaks.  Repair leaks if found.

Do not check for gas leaks with an open flame.
Use  a  bubble  test.    Failure  to  check  for  gas
leaks can cause severe personal injury, death
or substantial property damage.

15. Reattach the air inlet elbow to the venturi.

16. Reposition the Control Module panel and reat-

tach the front jacket panel.

17. Turn  the  electrical  power  “ON”  to  the  PRES-

TIGE to return the unit back into service.

COMBUSTION TEST/ADJUSTEMENT 

It is recommended that the installer perform a com-
plete  combustion  check  to  ensure  the  following
combustion  levels  are  met  at  high  and  low  inputs
and the burner is operating at optimum conditions.

NOTICE

WARNING

Gas Valve 

Blower

Venturi / Blower Gasket

Venturi

Fig. 3: Venturi Assembly

PRESTIGE

Model

Venturi

Size

PS 60

055

PS 110

002

PE 110
PS 175

052

PS 250

051

Table 1: Venturi Sizes

Natural Gas

Propane

O2 Min.

2.30%

2.70%

O2 Max.

5.30%

4.70%

CO2 Min.

8.80%

10.70%

CO2 Max.

10.50%

12.00%

CO Max.

100 ppm

100 ppm

Table 2: Recommended Combustion Levels