background image

PRESTIGE Venturi

Replacement Kit 

4

The  combustion  testing  and  adjustments
must  be  performed  by  a  qualified  installer,
service  agency  or  the  gas  supplier. All  com-
bustion measurements must be perform with
calibrated equipment to ensure proper read-
ings and accuracy.

Failure  to  perform  a  complete  combustion
test  at  both  high  and  low  input  rates  may
result in incomplete combustion and the pro-
duction  of  carbon  monoxide,  which  can
cause  severe  personal  injury,  death  or  sub-
stantial property damage.

MCBA Instructions

1. Manually  place  the  boiler  into  High  fire  mode

by pressing the MODE button with  “+”  button
simultaneously  on  the  control  panel  display
while in the standby (STBY) mode.

The  control  panel  will  display  a  H  followed
by  the  current  boiler  temperature  when
placed into high fire test mode.

2. If  the  combustion  levels  during  High  fire  are

outside  the  recommended  combustion  settings
adjust the THROTTLE SCREW (see Fig. 4) as
follows:

Counter-clockwise  adjustment  of  the  THROT-
TLE SCREW at high fire:

O2 decreases and C02 increases

Clockwise  adjustment  of  the  THROTTLE
SCREW at high fire:

O2 increases and CO2 decreases

3. Once  the  combustion  level  is  set  at  High  fire,

manually place the boiler into Low fire mode by
pressing  the  MODE  button  with  “-”  button

simultaneously  on  the  control  display  while  in
the standby (STBY) mode.

The  control  panel  will  display  a  L  followed
by  the  current  boiler  temperature  when
placed into low fire test mode.

4. If the combustion level at Low fire is not with-

in +/- 0.2% of the combustion level measured at
High  fire,  remove  the  offset  cover  screw  and
adjust the plastic 

OFFSET SCREW

using a T-

40 Torx wrench (see Fig. 4) as follows:

Counter-clockwise  adjustment  of  OFFSET
SCREW at low fire:

O2 increases and CO2 decreases

Clockwise  adjustment    of  OFFSET  SCREW  at
low fire:

O2 decreases and CO2 increases

5. Press the “+” and “-” buttons simultaneously to

shutdown the burner.

WARNING

NOTICE

NOTICE

WARNING

Offset Pressure

Cover Screw

Throttle

Screw

Fig. 4: Combustion Adjustment - Prestige Burner

Отзывы: