background image

PRESTIGE Venturi

Replacement Kit 

5

Revised Date: 5/30/12

2011-51 Prestige Venturi Replacement Kit_1111

Trimax Instuctions

1. Press the round INSTALLER button. See Fig. 5.

2.  Enter  the  installer  access  code  “054”  by  using

the 

LEFT

and 

RIGHT

buttons to select a digit

and the 

UP

and 

DOWN

buttons to change the

digit.  Press the 

OK

button to enter the access

code.

3. Press  the 

RIGHT

button  to  highlight  the

Manual  Operation  icon

then  press  the 

OK

button.

4.  Press  the 

OK

button  while  the  FAN  icon  is

highlighted  to  manually  fire  the  burner  and
power the CH circulator.

An adequate CH load must be present to dissi-
pate  the  heat  generated  during  the  combustion
test.  If an adequate CH load is not available, an
indirect water heater can be used to dissipate the
heat  by  creating  a  DHW  call  which  will  enable
the DHW circulator.

5.  Press the 

RIGHT

button to adjust the firing rate

to  100%.    Hold  down  the   

RIGHT

button  to

rapidly increase the firing rate.

6. If  the  combustion  levels  during  High  fire  are

outside  the  recommended  combustion  settings
adjust the THROTTLE SCREW (see Fig. 4) as
follows:

Counter-clockwise  adjustment  of  the  THROT-
TLE SCREW at high fire:

O2 decreases and C02 increases

Clockwise  adjustment  of  the  THROTTLE
SCREW at high fire:

O2 increases and CO2 decreases

7. Once  the  combustion  level  is  set  at  High  fire,

manually place the boiler into Low fire mode by
pressing  the 

LEFT

button  to  adjust  firing  rate

down to 0%.

8. If  the  combustion  level  during  Low  fire  is  not

/-0.2 of the combustion level measured
at High fire, remove the offset cover screw and
adjust the plastic OFFSET SCREW (see Fig. 4)
using a T-40 Torx wrench as follows:

Counter-clockwise  adjustment  of  OFFSET
SCREW at low fire (0% firing rate):

O2 increases and CO2 decreases

Clockwise  adjustment    of  OFFSET  SCREW at
low fire (0% firing rate):

O2 decreases and CO2 increases

9. Press the 

OK

button while the fan icon is high-

lighted to shutdown the burner.

10. Press the 

LEFT

or 

RIGHT

button to highlight

the  home  screen  icon

to  exit  the  service

mode.

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

NOTICE

 

   

 

 

   

 

 

   

 

 

   

 

 

  

 

 

  

 

 

  

 

 

  

  

 

 

Installer
Button

Fig. 5: Trimax Navigation Buttons

Manual Operation

Released

Off

Off

Off

CH

CH1

FAN

DHW

SYS

CH2