23
Parameter 40 Adjustment
To change Parameter 40, requires entering the Access
Code as outlined on page 2. After entering the Access
Code, press the MODE button until the display shows
PARA
. Press the STEP button to reach Parameter 40.
Press the “+” or “–“ button to change the setting of
Parameter 40 to the desired setting. Press the STORE
button and confirm that the display blinks to indicate the
setting has been stored.
The parameter setting is multiplied by 10.2 seconds
to reach the actual CH call blocking time. For exam-
ple, a setting of 3 results in a CH call blocking time
of 30.6 seconds.
NOTICE
CH CALL BLOCKING TIME
(PARAMETER 40)
After the completion of a heating call, a time delay peri-
od before responding to the next CH call can be set with
Parameter 40.
CH Call Blocking Time
(Parameter 40)
During the CH call blocking time, the burner will not
respond to a heating call. The CH circulator will contin-
ue to operate for a heating call. This blocking time has
no affect on domestic calls. This CH call blocking fea-
ture prevents short cycling of the burner and extends the
life of the burner components.