20
CH BLOCK TEMPERATURE SETTING
(PARAMETER 18)
This boiler shutdown feature is available when a con-
stant CH demand is selected for the CH operating signal
with Parameter 45.
CH Block Temperature Setting
(Parameter 18)
When a constant CH demand is selected for the CH
operating signal with Parameter 45, a continuous heat-
ing call is generated. The heating call will end when the
boiler CH setpoint falls below the temperature set by this
parameter. The heating call will resume when the boiler
CH setpoint rises above the temperature set by this
parameter.
Parameter 18 Adjustment
To change Parameter 18, requires entering the Access
Code as outlined on page 2. After entering the Access
Code, press the MODE button until the display shows
PARA
. Press the STEP button to reach Parameter 18.
Press the “+” or “–“ button to change the setting of
Parameter 18 to the desired setting. Press the STORE
button and confirm that the display blinks to indicate the
setting has been stored.
The factory setting of 32°F is the OFF position. The
boiler will operate with a continuous heating call.
NOTICE
30
50
70
90
110
130
150
170
(UORKX
:KSVKXGZ[XK
,
3G^
Min. 32
'JP[YZGHRK8GTMK
6GXGSKZKX
)G
RI[
RG
ZK
J
(U
ORK
X5
VK
XG
ZOT
M
:K
S
VK
XG
Z[
XK
(UORKX5,,
5[ZJUUX:KSVKXGZ[XK
=GXSKX
)UURKX
F
F
Fig. 3: Setting the Block Temperature Set Point