DHW CIRCULATOR POST PUMP TIME
PERIOD
(PARAMETER 33)

At the completion of a domestic call, the DHW circulator
will continue to operate for a time period set by
Parameter 33.  

DHW Circulator Post Pump Time
(Parameter 33)

The post pump feature allows the heat remaining in the
boiler to be sent to the Indirect Water Heater, thus pre-
venting overheating in low temperature space heating
applications.

When adjusting the DHW circulator post pump time,
it is strongly recommended that the installer utilize
a thermostatic mixing valve on the hot water outlet
of the Indirect Water Heater.  Failure to comply
could result in severe personal injury, death, or sub-
stantial property damage.

Parameter 33 Adjustment

To change Parameter 33, requires entering the Access
Code as outlined on page 2.  After entering the Access
Code, press the MODE button until the display shows

PARA

.  Press the STEP button to reach Parameter 33.

Press the “+” or “–“ button to change the setting of
Parameter 33 to the desired setting.  Press the STORE
button and confirm that the display blinks to indicate the
setting has been stored.

The parameter setting is multiplied by 10.2 seconds
to reach the actual post pump time.  For example,
the factory setting of 3 results in a post pump time
of 30.6 seconds.

NOTICE

DANGER

DHW NTC SENSOR ERROR CODES

Two error codes are possible when an NTC sensor is
selected for the DHW operating signal with Parameter
46.

If a short circuit is detected across the Indirect Water
Heater sensor terminals of the Prestige, a soft lockout
will occur.  This lockout will be indicated by a boiler sta-

tus code of 

9

, with an alternating error code of 

b_33

.

Check the sensor wiring for a possible short circuit.
Verify the resistance of NTC Sensor.

If an open circuit is detected across the Indirect Water
Heater sensor terminals of the Prestige, a soft lockout
will occur.  This lockout will be indicated by a boiler sta-

tus code of 

9

, with an alternating error code of 

b_38

.

Check sensor wiring for continuity and proper termina-
tion at Prestige terminal strip.  Verify the resistance of
NTC Sensor.

During a soft lockout, the burner function is blocked
from both domestic and heating calls.  The CH cir-
culator will continue to operate during a heating call.
Both error codes will automatically reset once the
condition has been corrected.

FROST / FREEZE PROTECTION OF
INDIRECT WATER HEATER

This feature is only available when an NTC sensor is
selected for the DHW operating signal with Parameter
46.  If the domestic hot water temperature falls to 38°F,
the burner and DHW circulator will operate.  The burner
will operate at its minimum input and the circulator will
operate until the domestic hot water temperature reach-
es 50°F.  At that point, the burner and circulator will be
turned off.  This feature is always active even if the
domestic hot water function has been disabled with
Parameter 2.

NOTICE

9

Содержание Prestige Supplement - Type 5 MCBA

Страница 1: ...l instructions within this document and within the PRESTIGE Boiler Installation and Maintenance Manual before pro ceeding It is recommended to follow the procedures in the steps given skipping or miss...

Страница 2: ...Entering MCBA Access Code 2 Revising Application Setting 3 Domestic Hot Water DHW Parameters 4 Domestic Hot Water Applications 5 11 Central Heating CH Parameters 12 Central Heating Applications 13 23...

Страница 3: ...to the equipment but not related to personal injury hazards Indicates recommendations made by Triangle Tube for the installers which will help to ensure optimum operation and longevity of the equipmen...

Страница 4: ...l the display shows PARA Once the display shows PARA press the STEP button to reach the appropriate parameter The display should follow the fol lowing sequence Press STEP once 1140 Press STEP x2 2_01...

Страница 5: ...n of domestic hot water The next section covers the parameters related to space heating The installer should record each parameter revision using the worksheet located in the back of the manual Prior...

Страница 6: ...4 DOMESTIC HOT WATER DHW PARAMETERS...

Страница 7: ...not respond to a domestic call from an Indirect Water Heater Both the burner and DHW circu lator will remain off during a domestic call The boiler will continue to respond to a call for heat from the...

Страница 8: ...setting has been stored When selecting continuous DHW circulator opera tion the installer should install a thermostatic mixing valve on the outlet of the Indirect Water Heater to pre vent a potential...

Страница 9: ...monitored and compared to the domestic hot water setpoint to deter mine if a domestic call is needed The domestic water temperature can be monitored on the boiler display via item 3 of the INFO menu...

Страница 10: ...omestic hot water tem perature goes above Parameter 1 plus Parameter 39 A low setting of Parameter 39 will result in a minimal overshoot of the domestic hot water setpoint A high set ting of Parameter...

Страница 11: ...NTC sensor is selected for the DHW operating signal with Parameter 46 If a short circuit is detected across the Indirect Water Heater sensor terminals of the Prestige a soft lockout will occur This l...

Страница 12: ...a domestic call a time delay period before responding to a heating call can be set with Parameter 42 DHW to CH Call Blocking Time Parameter 42 During the DHW to CH call blocking time the burner will...

Страница 13: ...ity timeout setting has been reached priority will shift to the heating call If both calls continue the priority will switch back to the domestic call after reaching the DHW priority timeout setting A...

Страница 14: ...12 CENTRAL HEATING CH PARAMETERS...

Страница 15: ...32 CH Call Blocking Time Parameter 40 b Outdoor Reset The CH Setpoint will vary between the CH Maximum Boiler Operating Setpoint Parameter 4 and the CH Minimum Boiler Operating Setpoint Parameter 10...

Страница 16: ...espond to a domestic call from an Indirect Water Heater Burner Enabled CH Pump Continuous Parameter 3 03 The burner will respond to a heating call The burner will operate during a heating call The CH...

Страница 17: ...is connected the CH Minimum Boiler Operating Setpoint becomes the boiler setpoint on the CH Reset Curve Warmest Day CH Reset Curve Coldest Day Parameter 11 This parameter is not applicable if an outd...

Страница 18: ...ng Press the STORE button and confirm that the display blinks to indicate the setting has been stored Parameter 12 Adjustment To change Parameter 12 requires entering the Access Code as outlined on pa...

Страница 19: ...KZKX 5 ZJUUX KSVKXGZ XK GXSKX UURKX UORKX KSVKXGZ XK Fig 1 Setting the Boiler Operating Limits 60 100 80 60 40 20 20 0 80 100 120 140 160 180 3G 3OT G R I R G Z K J U O R K X 5 V K X G Z O T M K S V K...

Страница 20: ...external modulating boiler controller wired directly to the boiler 0 10 VDC Analog Signal on AM 4 Parameter 45 03 The heating call is initiated from an external modulating boiler controller wired to...

Страница 21: ...Press the STEP button to reach Parameter 13 Press the or button to change the setting of Parameter 13 to the desired setting Press the STORE button and confirm that the display blinks to indicate the...

Страница 22: ...arameter 18 Adjustment To change Parameter 18 requires entering the Access Code as outlined on page 2 After entering the Access Code press the MODE button until the display shows PARA Press the STEP b...

Страница 23: ...and will raise the CH setpoint by 18 F if the call for heat in not satisfied in the time period set by this parameter Parameter 19 Adjustment To change Parameter 19 requires entering the Access Code...

Страница 24: ...on and confirm that the display blinks to indicate the setting has been stored The factory setting of 00 F is the OFF position The CH setpoint will not decrease if the room thermostat terminals are op...

Страница 25: ...by 10 2 seconds to reach the actual CH call blocking time For exam ple a setting of 3 results in a CH call blocking time of 30 6 seconds NOTICE CH CALL BLOCKING TIME PARAMETER 40 After the completion...

Страница 26: ...ut Code Consult the Prestige Installation Maintenance Manual or Troubleshooting Guide for Error Code descriptions Item 2 displays the mode the boiler was operating in when the error occurred Item 3 di...

Страница 27: ...25 PARAMETER WORKSHEET...

Страница 28: ...56 228 8881 Fax 856 228 3584 E mail Sales triangletube com For domestic water snow melting radiant floor refrigeration Plates made of stainless steel with a 99 9 copper and brazed ensuring a high resi...

Отзывы: