49
Start-Up Procedures
Error (Hard Lockout) Mode
If a serious fault occurs, the system enters a
hard lockout condition which requires a manu-
al reset by pressing the RESET button. A hard
lock is indicated by displaying an E for the first
digit, followed by the error code.
For a detailed description of the error codes, ref-
erence the PRESTIGE Solo Troubleshooting
Guide.
The boiler freeze protection feature is
disabled during a Hard Lockout, howev-
er the CH circulator will operate.
During a hard lockout or low water con-
dition the boiler will not re-start without
service. If the heating system is left unat-
tended in cold weather appropriate safe-
guards or alarms should be installed to
prevent property damage.
CAUTION
CAUTION
Gas valve harness not properly connected
Failed ignition after 5 attempts
Power supply lost after lockout occured
Internal control failure
Internal control failure
E
E
02
03
04
08
09
E
E
E
Display
Hard Lockout
Internal control failure
05
E
Internal control failure
06
E
Internal control failure
07
E
Flame detected prior to burner startup
E 00
Internal control failure
External limit (terminals 13 & 14) is OPEN
Blower signal does not reset to zero
No blower signal present
Supply Temperature sensor is short circuited
11
12
15
16
29
28
E
E
E
E
E
E
Flue Temperature exceeds 250 F
52
E
Internal control error - failure to read parameters
61
E
Return Temperature sensor is short circuited
Supply Temperature sensor is OPEN
Return Temperature sensor is OPEN
Internal control failure
Internal control failure
Inadequate power supply to the fan
E
E
31
32
36
37
44
60
65
E
E
E
E
E
Flue Temperature sensor is short circuit
40
E
Return Temperature exceeds 212 F
Supply Temperature increased too rapidly
Internal control failure
Internal control failure
Internal control failure
Internal control failure
Internal control failure
17
19
25
13
E
E
E
E
Supply Temperature exceeds 212 F
18
E
E 14
Flue Temperature sensor is OPEN
35
E
E
Internal control failure
15
E
Supply or Return Temperature sensor drift
23
Invalid power frequency
Supply or Return Temperature failure
Supply or Return Temperature not changing
13
1
1
1
1
1
22
24
E
E
E
Содержание Prestige Slol 250
Страница 61: ...55 Factory Setting Parameters FACTORY SETTING FOR PARAMETERS ...
Страница 72: ...65 Replacement Parts 5 9 8 1 3 5 2 6 7 Fig 26 PRESTIGE Solo Jacket Components ...
Страница 73: ...66 Replacement Parts 8 5 9 2 3 4 4 6 7 1 Fig 27 PRESTIGE Solo 60 Internal Components ...
Страница 74: ...67 Replacement Parts 8 5 4 4 10 9 7 1 3 2 6 Fig 27A PRESTIGE Solo 175 250 Internal Components ...
Страница 75: ...68 Replacement Parts 8 7 10 1 2 3 4 4 5 6 9 Fig 27B PRESTIGE Solo 399 Internal Components ...
Страница 77: ...70 Replacement Parts 7 6 9 1 2 10 12 13 4 3 5 8 Fig 28A PRESTIGE Solo 399 Burner Components ...
Страница 78: ...71 3 Fig 29 PRESTIGE Solo Electronic Components Replacement Parts ...
Страница 80: ...73 Product Specifications Front View PRESTIGE Solo 175 250 ...
Страница 83: ...76 Product Specifications Side View PRESTIGE Solo 175 250 ...