![TriangleTube Prestige Slol 250 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/triangletube/prestige-slol-250/prestige-slol-250_installation-and-maintenance-manual_1160001043.webp)
37
Start-Up Preparation
SECTION IX - Start-Up Preparation
Check Boiler System Water Chemistry
Do not use petroleum-base cleaning or
sealing compounds in the boiler system.
Damage to seals and gaskets in the sys-
tem components could occur, resulting in
substantial property damage.
System water including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
Water pH Level 6.0 to 8.0
Maintain the boiler water pH between 6.0 and
8.0. Check using litmus paper or contact a water
treatment company for a chemical analysis.
If the pH does not meet this requirement, do
not operate the PRESTIGE Solo or leave the
unit filled until the condition is corrected.
Water Hardness Less Than 7 Grains
For areas with unusually hard water (hardness
above 7 grains) consult a water treatment
company.
Chlorinated Water
Do not use the PRESTIGE Solo to heat a
swimming pool or spa directly.
Maintain the chlorine level of the water at lev-
els considered safe for drinking.
Flush Boiler and Domestic System to
Remove Sediment
The installer must flush the boiler system to
remove any sediment to allow proper operation
of the PRESTIGE Solo .
Flush the systems until the water runs clean
and is free of sediment.
For zoned systems, each zone should be
flushed through a purge valve. Purge valves
and isolation valves should be installed on each
zone to allow proper flushing of the system.
Check and Test Antifreeze
For boiler systems containing antifreeze solu-
tions, follow the antifreeze manufacturer’s
instructions in verifying the inhibitor level and
to ensure the fluid characteristics are within
specification requirements.
Due to the degradation of inhibitors over time,
antifreeze fluids must be periodically replaced.
Refer to the manufacturer of the antifreeze for
additional instructions.
System water including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
NOTICE
NOTICE
WARNING
Содержание Prestige Slol 250
Страница 61: ...55 Factory Setting Parameters FACTORY SETTING FOR PARAMETERS ...
Страница 72: ...65 Replacement Parts 5 9 8 1 3 5 2 6 7 Fig 26 PRESTIGE Solo Jacket Components ...
Страница 73: ...66 Replacement Parts 8 5 9 2 3 4 4 6 7 1 Fig 27 PRESTIGE Solo 60 Internal Components ...
Страница 74: ...67 Replacement Parts 8 5 4 4 10 9 7 1 3 2 6 Fig 27A PRESTIGE Solo 175 250 Internal Components ...
Страница 75: ...68 Replacement Parts 8 7 10 1 2 3 4 4 5 6 9 Fig 27B PRESTIGE Solo 399 Internal Components ...
Страница 77: ...70 Replacement Parts 7 6 9 1 2 10 12 13 4 3 5 8 Fig 28A PRESTIGE Solo 399 Burner Components ...
Страница 78: ...71 3 Fig 29 PRESTIGE Solo Electronic Components Replacement Parts ...
Страница 80: ...73 Product Specifications Front View PRESTIGE Solo 175 250 ...
Страница 83: ...76 Product Specifications Side View PRESTIGE Solo 175 250 ...