39
Start-Up Preparation
Check For Gas Leaks
Prior to start-up and during initial opera-
tion, smell near the floor and around the
unit for gas odorant or any unusual odor.
Do not proceed with the start-up if there
is any indication of a gas leak. Any leaks
found must be repaired immediately.
Propane installations only - The propane
supplier mixes an odorant with the
propane to make its presence detectable.
In some cases the odorant can fade and
the gas may no longer have an odor.
Prior to start-up of the unit and periodi-
cally after start-up have the propane
supplier check and verify the odorant
level.
Check Thermostat Circuit
-
Disconnect the external thermostat wires
from the 24V terminal strip on the wiring
panel.
-
Connect a voltmeter across the wire ends of
the external thermostat wiring.
-
Close each thermostat, zone valve and
relay in the external circuit one zone at a
time and check the voltage reading across
the wire ends.
-
There should
NEVER
be voltage measured
at the wire ends.
-
If voltage is measured at the panel under any
condition, check and correct the external
wiring.
In systems using 3-wire zone valves,
backfeed of voltage to the unit is a com-
mon problem. Use an isolation relay to
prevent voltage from the external circuit
entering the PRESTIGE Solo control
panel.
-
Reconnect the external thermostat
wires to the 24V terminal strip on the
wiring panel.
Inspection of Condensate Drain Assembly
1. Inspect and ensure the Condensate Drain
Assembly is properly installed as described
on page 25 and shown in Fig. 15 on page
26.
2. Remove the plug from the Condensate
Drain Assembly and fill with fresh water.
The condensate drain assembly must be
filled with water when the PRESTIGE
Solo is in operation. The condensate
drain assembly prevents flue gas emis-
sions from entering the condensate line.
Failure to ensure trap is filled with water
could result in severe personal injury or
death.
3. Re-Install plug in condensate drain assem-
bly.
NOTICE
NOTICE
WARNING
WARNING
Содержание Prestige Slol 250
Страница 61: ...55 Factory Setting Parameters FACTORY SETTING FOR PARAMETERS ...
Страница 72: ...65 Replacement Parts 5 9 8 1 3 5 2 6 7 Fig 26 PRESTIGE Solo Jacket Components ...
Страница 73: ...66 Replacement Parts 8 5 9 2 3 4 4 6 7 1 Fig 27 PRESTIGE Solo 60 Internal Components ...
Страница 74: ...67 Replacement Parts 8 5 4 4 10 9 7 1 3 2 6 Fig 27A PRESTIGE Solo 175 250 Internal Components ...
Страница 75: ...68 Replacement Parts 8 7 10 1 2 3 4 4 5 6 9 Fig 27B PRESTIGE Solo 399 Internal Components ...
Страница 77: ...70 Replacement Parts 7 6 9 1 2 10 12 13 4 3 5 8 Fig 28A PRESTIGE Solo 399 Burner Components ...
Страница 78: ...71 3 Fig 29 PRESTIGE Solo Electronic Components Replacement Parts ...
Страница 80: ...73 Product Specifications Front View PRESTIGE Solo 175 250 ...
Страница 83: ...76 Product Specifications Side View PRESTIGE Solo 175 250 ...