52
Maintenance Procedures
Check Burner Flame
Remove burner cover and inspect the
flame through the observation port on the
burner mounting plate.
If flame pattern does not cover the entire
burner surface, shut the appliance down
and allow it to cool thoroughly.
Close the manual gas valve on the gas sup-
ply line and disconnect the gas piping to
remove the burner assembly from the appli-
ance. Remove control cover and disconnect
electrical quick connects going to burner
assembly.
Remove two nuts securing the burner
mounting plate. See warning on page 53.
Remove the burner assembly and screws to
the burner head. Remove burner head and
inspect for deterioration. Use compressed
air or a vacuum to clean the burner head.
Remove the venturi and gas valve assem-
bly from the blower.
Use the vacuum cleaner or compressed air
to clean the interior of the blower assembly.
Inspect the blower blades to ensure they are
clean and not damaged.
Re-assemble the venturi and gas valve onto
the blower. Ensure the venturi gasket is in
good condition and positioned correctly.
Re-assemble the burner head onto the burn-
er- mounting plate. Ensure the burner head
gasket is in good condition and positioned
correctly.
Secure burner mounting plate to the appli-
ance with two nuts. Re-assemble the elec-
trical quick connects to burner assembly,
control cover and gas supply. Open the
manual gas valve and place the appliance
back into service.
Verify flame pattern & re-install burner
cover.
Check Flame Signal
The flame signal should be at least 2
µ Α.
Refer to the MODULATING DELTA
Trouble-shooting Guide for information on
checking the flame signal.
Check the ignitor for fouling or damaged
insulation if a low flame signal is read.
Check Combustion Levels
Refer to page 36 of this manual for mea-
suring combustion levels and burner
adjustments.
Review With Owner
Ensure the owner understands the impor-
tance to perform the maintenance schedule
specified in this manual.
Remind the owner of the importance to call
a licensed contractor should the appliance
or system exhibit any unusual behavior.