TPLP
60Hz
RECOMMENDED EXPANSION VALVE
SELECTIONS -
MEDIUM TEMP. MODELS
Above selections based on:
1) 100°F (38°C) vapor free liquid entering expansion valve
2) 110°F (43°C) Condensing temperature
3) 8 -12°F (4.4 -6.7°C) evaporator TD
If correct nozzle is not
available, the proper
orifice size can be
drilled in the field using
the following chart
NOZZLE
ORIFICE
No.
DRILL
SIZE
IN.
1/2
.070
3/4
.086
1
.0995
1-1/2
.120
2
.1406
2-1/2
.157
3
.172
4
.199
5
.211
6
.242
8
.266
10
.281
MODEL
FACTORY
INSTALLED
NOZZLE
R404A
R507
R407A
R407C
R22
R134a
104M
N/A
HFESC 1/4 SC
HFESC 1/2 HC
HFESC 1/2 MC
106M
L-1/2
HFESC 1/2 SC
HFESC 1/2 HC
HFESC 3/4 MC
107M
L-1/2
HFESC 1/2 SC
HFESC 1/2 HC
HFESC 3/4 MC
209M
L-3/4
HFESC 1 SC
HFESC 1 HC
HFESC 3/4 MC
211M
L-1
HFESC 1 SC
HFESC 1 HC
HFESC 1 MC
214M
L-1
HFESC 1-1/4 SC
HFESC 1-1/2 HC
HFESC 1 MC
317M
L-1 1/2
HFESC 1-1/2 SC
HFESC 1-1/2 HC
HFESC 1-1/2 MC
320M
L-1 1/2
HFESC 1-1/2 SC
HFESC 2 HC
HFESC 1-3/4 MC
423M
L-2
HFESC 2 SC
HFESC 2 HC
HFESC 1-3/4 MC
426M
L-2
HFESC 2 SC
HFESC 2-1/2 HC
HFESC 2-1/2 MC
532M
L-2 1/2
HFESC 3-1/2 SC
HFESC 2-1/2 HC
HFESC 2-1/2 MC
639M
G-3
HFESC 3-1/2 SC
HFESC 3 HC
HFESC 4 MC
ALCO
SPORLAN
MODEL
FACTORY
INSTALLED
NOZZLE
R404A
R507
R407A
R407C
R22
R134a
104M
N/A
EBQE-AA-*C
EBQE-AAA-VC
EBQE-AAA-JC
106M
L-1/2
EBQE-AA-*C
EBQE-AA-VC
EBQE-AA-JC
107M
L-1/2
EBQE-A-*C
EBQE-AA-VC
EBQE-AA-JC
209M
L-3/4
EBQE-A-*C
EBQE-AA-VC
EBQE-AA-JC
211M
L-1
EBQE-A-*C
EBQE-A-VC
EBQE-A-JC
214M
L-1
EBQE-B-*C
EBQE-A-VC
EBQE-A-JC
317M
L-1 1/2
EBQE-B-*C
EBQE-A-VC
EBQE-A-JC
320M
L-1 1/2
EBQE-B-*C
EBQE-B-VC
EBQE-A-JC
423M
L-2
EBQE-B-*C
EBQE-B-VC
EBQE-A-JC
426M
L-2
EBQE-C-*C
EBQE-B-VC
EBQE-B-JC
532M
L-2 1/2
EBQE-C-*C
EBQE-B-VC
EBQE-B-JC
639M
G-3
EBQE-C-*C
EBQE-C-VC
EBQE-C-JC
* Varies with refrigerant: S = R404A, P = R507
MODEL
FACTORY
INSTALLED
NOZZLE
R404A
R507
R407A
R407C
†
R22
R134a
104M
N/A
TUAE-R404A-4-N
TUAE-R22-4-N
TUAE-R134a-4-N
106M
L-1/2
TUAE-R404A-5-N
TUAE-R22-5-N
TUAE-R134a-5-N
107M
L-1/2
TUAE-R404A-6-N
TUAE-R22-5-N
TUAE-R134a-5-N
209M
L-3/4
TUAE-R404A-7-N
TUAE-R22-6-N
TUAE-R134a-6-N
211M
L-1
TUAE-R404A-7-N
TUAE-R22-6-N
TUAE-R134a-6-N
214M
L-1
TUAE-R404A-8-N
TUAE-R22-7-N
TUAE-R134a-7-N
317M
L-1 1/2
TUAE-R404A-8-N
TUAE-R22-8-N
TUAE-R134a-8-N
320M
L-1 1/2
TUAE-R404A-9-N
TUAE-R22-8-N
TUAE-R134a-8-N
423M
L-2
TUAE-R404A-9-N
TUAE-R22-8-N
TUAE-R134a-9-N
426M
L-2
TCAE-R404A-TC1-N
TUAE-R22-9-N
TUAE-R134a-9-N
532M
L-2 1/2
TCAE-R404A-TC2-N
TUAE-R22-9-N
TCAE-R134a-TC1-N
639M
G-3
TCAE-R404A-TC3-N
TCAE-R22-TC1-N
TCAE-R134a-TC2-N
DANFOSS
†
If using 407C, superheat setting must be adjusted by turning 1 - 1.5 turns clockwise.
23/12/16
T30-TPLP-PDI-11