60Hz
TPLP
CAPACITY DATA -
ALL MODELS
Medium Temperature Models - Capacity @ 6 F.P.I. *
Capacities rated using 10°F
(5.6°C)
TD & 100°F
(38°C)
liquid temperature.
Capacities at other TD within a range of 8 to 15 °F
(4.4 to 8.3°C)
are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
For capacities at TD outside of range 8 to 15 °F
(4.4 to 8.3°C)
, or liquid temperature lower than 75°F
(24°)
, consult factory.
Capacities for R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated suction
temperature and the temperature feeding the evaporator. For dew point ratings, consult factory.
Medium Temp. Models
104M
106M
107M
209M
211M
214M
317M
320M
423M
426M
532M
639M
Number Of Fans
1
1
1
2
2
2
3
3
4
4
5
6
Capacity
BTUH
(WATTS)
Evap
Temp.
25°F
(-4°C)
R407A
4090
5230
6460
8170
10450
13300
16200
19000
21900
24700
30400
37100
(1197)
(1530)
(1891)
(2394)
(3059)
(3895)
(4731)
(5567)
(6403)
(7230)
(8902)
(10830)
R407C
3870
4950
6120
7740
9900
12600
15400
18100
20800
23500
28900
35200
(1134)
(1449)
(1791)
(2268)
(2898)
(3690)
(4482)
(5274)
(6066)
(6849)
(8433)
(10260)
R404A
R507
4300
5500
6800
8600
11000
14000
17000
20000
23000
26000
32000
39000
(1260)
(1610)
(1990)
(2520)
(3220)
(4100)
(4980)
(5860)
(6740)
(7610)
(9370)
(11400)
R22
4090
5230
6460
8170
10500
13300
16200
19000
21900
24700
30400
37100
(1197)
(1530)
(1891)
(2394)
(3059)
(3895)
(4731)
(5567)
(6403)
(7230)
(8902)
(10830)
Air Flow
CFM
(
L/S)
1010
(470)
950
(450)
900
(430)
2020
(950)
1910
(900)
1800
(850)
2860
(1350)
2700
(1270)
3810
(1800)
3600
(1700)
4500
(2120)
5400
(2550)
Refrigerant **
Charge
R407A
LB. (KG)
0.7
(0.3)
1.1
(0.5)
1.5
(0.7)
1.3
(0.6)
1.4
(0.6)
2.0
(1.2)
3.0
(1.4)
4.0
(1.8)
3.9
(1.8)
3.3
(2.4)
6.5
(3.0)
7.8
(3.5)
R407C
R404A
R507
R22
R134a
0.99
0.92
0.93
1.02
1.03
Low Temperature Models - Capacity @ 6 F.P.I. *
Low Temp. Models
104L
105L
106L
207L
209L
211L
314L
317L
419L
422L
527L
631L
Number Of Fans
1
1
1
2
2
2
3
3
4
4
5
6
Capacity
BTUH
(WATTS)
Evap
Temp.
-20°F
(-29°C)
R407A
3610
4560
5510
7030
8550
10500
13300
16200
18100
20900
25700
29500
(1055)
(1340)
(1615)
(2062)
(2508)
(3059)
(3895)
(4731)
(5292)
(6118)
(7515)
(8626)
R404A
R507
3800
4800
5800
7400
9000
11000
14000
17000
19000
22000
27000
31000
(1110)
(1410)
(1700)
(2170)
(2640)
(3220)
(4100)
(4980)
(5570)
(6440)
(7910)
(9080)
Air Flow
CFM
(
L/S)
1010
(470)
950
(450)
900
(430)
2020
(950)
1910
(900)
1800
(850)
2860
(1350)
2700
(1270)
3810
(1800)
3600
(1700)
4500
(2120)
5400
(2550)
Refrigerant **
Charge
R407A
LB. (KG)
0.7
(0.3)
1.1
(0.5)
1.5
(0.7)
1.3
(0.6)
1.4
(0.6)
2.0
(1.2)
3.0
(1.4)
4.0
(1.8)
3.9
(1.8)
3.3
(2.4)
6.5
(3.0)
7.8
(3.5)
Low Temperature Models - Capacity @ 4 F.P.I. *
Low Temp. 4 FPI Models
103V
104V
105V
206V
208V
209V
312V
315V
416V
419V
523V
627V
Number Of Fans
1
1
1
2
2
2
3
3
4
4
5
6
Capacity
BTUH
(WATTS)
Evap
Temp.
-20°F
(-29°C)
R407A
2850
3900
4750
6080
7410
8840
11400
14300
15200
18100
21900
25700
(836)
(1140)
(1397)
(1786)
(2176)
(2584)
(3344)
(4171)
(4456)
(5292)
(6403)
(7515)
R404A
R507
3000
4100
5000
6400
7800
9300
12000
15000
16000
19000
23000
27000
(880)
(1200)
(1470)
(1880)
(2290)
(2720)
(3520)
(4390)
(4690)
(5570)
(6740)
(7910)
Air Flow
CFM
(
L/S)
1070
(510)
1010
(480)
950
(450)
2140
(1010)
2020
(950)
1910
(900)
3030
(1430)
2860
(1350)
4040
(1910)
3810
(1800)
4770
(2250)
5720
(2700)
Refrigerant **
Charge
R407A
LB. (KG)
0.7
(0.3)
1.1
(0.5)
1.5
(0.7)
1.3
(0.6)
1.4
(0.6)
2.0
(1.2)
3.0
(1.4)
4.0
(1.8)
3.9
(1.8)
3.3
(2.4)
6.5
(3.0)
7.8
(3.5)
* CAPACITY CORRECTION FACTORS FOR LOW TEMPERATURE UNITS
SATURATED SUCTION
TEMPERATURE °F (°C)
0
(-17.8)
-10
(23.3)
-20
(-28.9)
-30
(-34.4)
-40
(-40)
FACTOR
1.06
1.03
1.0
0.92
0.85
** REFRIGERANT CHARGE CONVERSION FACTORS
NO CORRECTION FACTOR REQUIRED FOR MEDIUM TEMP. UNITS
23/12/16
T30-TPLP-PDI-11