WIRING DIAGRAM - 208-230/1/60
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - MULTIPLE EVAPORATORS
MUST BE MADE
EVAP#2 FIELD MODIFICATION
WARNING
COMPR INTERLOCK
FOR ALL MODELS USING DEFROST HEATER CONTACTOR
THERMOSTAT
NOTE #4
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
1). USE COPPER CONDUCTORS ONLY
3). OVERCURRENT PROTECTION FOR
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
NOTES
2). USE 75°C WIRE (OR HIGHER)
MTR
FAN
FAN
MTR
FAN
MTR
DEFROST TERMINATION
CONTROL
(10.0A MAX.)
& FAN DELAY
FD-FAN DELAY
DT-DEFROST TERM
X
F
4
BK
GND.
C
FD
DT
BN
RD
(IF USED)
SWITCH
OR EQUIVALENT
PUMP DOWN
SPACE
(IF USED)
BREAKER
2
1
N
NOTE #3
TM
4
X
3
CIRCUIT
FUSE OR
DEFROST CLOCK
PARAGON # 8145
EVAPORATOR
OPTIONAL FACTORY
FACTORY WIRING
WIRING BY OTHERS
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
4-LP ED CONTACTOR MULTI 12/07
-TERMINAL BLOCK TERMINAL
-COMPONENT TERMINAL
CONDUCTORS/WIRING
TERMINALS
DATA PLATE FOR
MOTOR QUANTITY
EVAPORATOR
REFER TO
POWER PLUGS
FAN MOTOR
H2
NOTE #4
SOL VALVE
L2
L1
N.C.
LIQUID LINE
L2
T2
L1
C
T1
GND
OR BY OTHERS
AND WIRED ON EVAPORATOR
4.) MAY BE FACTORY INSTALLED-MOUNTED
DEFROST HEATERS
CIRCUIT
BREAKER
NOTE #3
FUSE OR
DEFROST HEATER
CONTACTOR
EVAPORATOR
MTR
FAN
MTR
FAN
FAN
MTR
FAN MOTOR
POWER PLUGS
EVAPORATOR
MOTOR QUANTITY
DATA PLATE FOR
REFER TO
GND.
4
DT
RD
DEFROST TERMINATION
DT-DEFROST TERM
FD-FAN DELAY
(10.0A MAX.)
CONTROL
& FAN DELAY
BK
FD
C
DEFROST HEATERS
F
X
BN
* Remove & Insulate
* Fan delay not used on second evap / use fan contactor if total fan amps exceeds 10A
PRIMARY
SECONDARY
FUSE OR
BREAKER
NOTE #3
CIRCUIT
H1
N
H2
H1
N
LIMIT
YL
3
(10.0A MAX.)
SWITCH
HEATER
WH
LIMIT
YL
3
(10.0A MAX.)
SWITCH
HEATER
WH
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
RELOCATE WHITE WIRE FROM
N AS SHOWN
SEE NOTE:
1
1
REMOVE AND INSULATE
2
AS SHOWN
2
TPLP
PSC
60Hz
23/12/16
T30-TPLP-PDI-11
- 14 -