IQ41x Installation Instructions - Configuring TG201251 Issue 5, 22-Aug-2014
5
InstallationInstructions-Configuring
IQ41x
16
Set up Ethernet Access Across Routers
(if required)
If the Lan is to be built across a router(s) details of devices
(on each subnet) must be specified to enable cross-router
communications.
Use IP Tool – see step 13 – to specify IP settings for up to 20
devices in the Remote Trend Devices list:
Parameter
Value
IP Address
If using dynamic (DHCP) addressing:
Enter the host name of the remote device.
If using static (fixed) addressing:
Enter the IP Address of the remote device,
in the format: xxx.xxx.xxx.xxx
Subnet Mask
The subnet mask for the remote device, in
the format: xxx.xxx.xxx.xxx
IP Tool Manual (TE200638)
17
SetuptrendAddressing
SingleIQ4orLanofIQ4sonethernet:
▪
Use IP Tool – see step 13 – to set the address (ensuring it
is unique on the Lan) and Lan number
IQ4s are given an address and Lan number in the factory. The
address is set in the range 11 to 119 on a rolling basis with the
Lan number set to 20. Therefore it may be necessary to set up
the address/Lan number as required.
Parameter
Range
Description
Address
1, 4 to 9, 11 to
119
Must be unique on Lan
Lan
number
1, 4 to 9, 11 to
119
Must be the same as all
devices it is to form a Lan with.
Note: Changing the Lan number and address will cause the
IQ4 to reset.
IP Tool Manual (TE200638)
IQTool Addresser Applet Manual
(TE201299)
LanofIQ4soncurrentloop:
▪
Run SET, right click the Lan of IQ4s in the
System View
select
Address IQ4 Device
to run the IQTool Addresser
Applet, and click to run the Discovery Wizard.
▪
Select either ‘Automatic Discovery’ (recommended) or
‘Manual Discovery’. If ‘Automatic Discovery’ was selected
you should also select Duplicate Address Resolution.
Automatic Discovery:
The tool will discover the devices,
and attempt to resolve duplicate addresses.
Manual Discovery:
Scan the bar code, or press the
Service Button for each controller.
WARNING
For /230 options hazardous
voltages exist when the unit is powered. Take
suitable precautions.
▪
If the Lan is not as expected it could be because of
installation related reasons, e.g. wiring faults, power
failure etc. Check the devices are operating correctly and
repeat discovery. If there are duplicate addresses add the
devices to the grid manually, using network address and
serial number. If necessary use SET’s System View to set
the Lan number, and IQTool to set the address.
LanIQ4andpreIQ4controllersoncurrentloop:
▪
Run SET, right click the Lan of IQ4s in the
System
View
and select
Address IQ4 Device
to run the IQTool
Addresser Applet.
▪
Add the IQ4 to the grid manually by clicking , specifying
the serial number, and address, and clicking .
▪
Use SET’s System View to set the Lan number.
It is recommended that at least two devices from each subnet
are specifed. For increased reliability details of additional
devices should be specified.
If static IP addressing is being used the list should contain the
devices with the lowest IP addresses.
The same list must be copied to other EINC type devices on
the network.
Hint: Ticking the check box next to the Remote Trend Devices
list retains the list in IP Tool, allowing it to be easily copied to
other devices:
2
ConFIguRAtIonPRoCeDuRe
(continued)
Draft