Installation
(for qualified installers only)
2 7
Travis Industries
4 0 2 0 8 1 2
9 3 5 0 8 1 1 0
Horizontal Terminations with 3 Vertical Elbows (Top Vent Configuration)
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.
NOTE:
• A total of three elbows must be used.
• No horizontal elbows may be used (a horizontal elbow is
defined as an elbow that directs the vent from a horizontal
direction to another horizontal direction).
• Two 45° elbows may be substituted for two of the 90° elbows.
• Horizontal sections require a 1/4" rise every 12" of travel.
• The maximum vertical height is 19'.
• The maximum horizontal length is 20'.
Horizontal Elbows are
NOT ALLOWED