Installation
(for qualified installers only)
39
© Travis Industries
4090807
100-01193_003
Mantel Requirements
•
The mantel (combustible or non-combustible) must be a minimum 50” above the base of the
fireplace (see Figure 28).
•
The maximum mantel depth is 12” (measured from the face).
Max. 12”
Base of the Fireplace
Min. 50”
Mantel
(combustible or non-combustible)
Combustible mantel columns (legs) that
protrude more than 3/4” from the glass
frame must meet the sidewall clearance (11”
from the glass frame). If they protrude 3/4”
or less, they must meet the facing clearance
(6-1/2” from the glass frame).
Non-combustible mantel columns do not
have a minimum clearance.
Figure 28