9
© Transtector 2017. All Rights Reserved.
Installation Procedure cont.
Installing Mounting Brackets
6. Secure mounting brackets to the sides of the panel using 4, #10-32 flat head screws provided. Torque fasteners to 23 inch
pounds. (see Figure 1)
Mounting Panel to Rack
7. Select a location for the AC Edge panel on the rack. Choose to mount power panels at topmost or highest possible rack position.
8. Note: Panel weighs approximately 17 lbs (7.7 kg). Take care to support the panel when installing panel to rack. Two persons may
be required in the following step.
9. Mount panel to rack using two sets of supplied fasteners per side (total of four #12-24 thread-forming, Phillips-head screws, split
lock washers, and flat washers.), as shown in Figure 2 below. Tighten screws to no greater than 35 inch pounds (~4.29 Newton
meter).
Torque Rating Chart
Fastener Connections
Maximum Torque (inch pounds)
Maximum Torque (Newton meters)
10-32
23 inch pounds
2.65 Newton meters
12-24
35 inch pounds
4.29 Newton meters
M6
55 inch pounds
6.2 Newton meters
Figure 1: Bracket Installation
Figure 2: Rack Mounting