Introduction
Transtector’s AC Edge 240 is a compact (2U) 240Vac secondary power distribution panel featuring two, 240Vac single phase 60A
input buses with dedicated neutrals. The AC Edge provides power for a wide range of local or remote, wireless and wireline, data
and mission critical communications applications. The panel fits 19 in. or 23 in. racks (23 in. brackets sold seperately; need 2X of P/N
2001-389).
The AC Edge supports the use of six breaker output positions per line. Accepted breakers listed in the table on Page 14 range from
1A to 10A with a UL classification of QVNU2. 5A and 10A breakers are available from Transtector, sold separately and installed by site
personnel (see Page 14 for part numbers).
The front of the panel contains six LEDs:
•
One on each line (labeled PWR, the LED is green when power is supplied to the unit and off when no power is supplied)
•
One on each line for tripped breaker indication (labeled FA, the LED is off during normal operation and red indicating a tripped
breaker)
•
One on each supression module (the LED is green when powered and functioning and red when powered and not functioning).
Form C dry contacts on the rear provide connectivity via a single 15-socket (female), D-type connector (HD-15) to remote audible/
visual alarm devices for announcing/displaying power, breaker, and bay failures. The supression modules can be replaced when
required (only when the unit is not powered, see page 14 for instructions).
Input ground connection made via a two hole compression lug on the back of the chassis. Chassis ground connection is tied to input
ground. All output connections are made via the IEC 320-C13 connectors on the back of the unit.