Outputs
22. The AC Edge power panel outputs consist of 6 IEC 320-C13 connectors per phase. The panel accepts 2 feeds at 240Vac each
with dedicated neutrals. Output positions accept standard IEC 320-C14 connectors (see Figure 5).
23. Connect opposite ends of output conductors to the output loads and label all wiring for clear identification.
24. Turn off or disable fuses, breakers, or other disconnect devices feeding power to the AC Edge panel.
Note: The following steps deal with breakers. Good practice involves turning off power to the panel when installing or replacing
breakers. When that is not possible, rely on and follow established operating company or regulatory practices. However, NEVER
install breakers in a live circuit with the operator handle switched on.
25. Remove blank cover over selected breaker position. Pull the handle of the blank cover to remove. See “Breaker Replacement”
on Page 14.
26. During installation of breakers, ensure that circuit breakers are switched off.
27. Install circuit breakers in the “off” position, with ON letters oriented towards the top of the unit and OFF towards the bottom.
28. When installing breakers, record the ratings and position on the designation card shown in Accessory Kit (see page 8). Insert
card into slot below breakers.
29. Disable AC Edge output loads at the equipment.
30. Turn on output breakers.
31. Turn on or enable fuses, breakers, or other disconnect devices to feed power to the AC Edge unit.
32. Verify that the PWR LEDs are on (green), FA (fuse alarm) LEDs are off, and surge module LED is on (green) for powered line and
off if not powered.
33. Turn off one of the breakers. Expect that the FA (fuse alarm) LED is on (red).
Check the FA (fuse alarm) terminals on the rear of the panel. Expect:
•
An open circuit (∞) between C and NC, and
• Continuity (0 Ohms) between C and NO.
34. Make sure all breakers are on.
35. Test power and polarity at the input of each output load.
36. Enable AC Edge ouput loads at equipment. Check loads for proper operation.
Installation Procedure cont.
Figure 5: IEC 320-C13 output positions and alarm connection