Circuit breakers are held in place by wide plastic barbs at the top and bottom of each breaker. The barbs lock into cutouts in the top
and bottom of the two breaker cages.
Transtector provides two breaker removal tools. The tools are used together to facilitate breaker removal by depressing the barbs while
prying out the breaker.
In use, slip one tool through the slot at the top of the breaker and one through the bottom of the breaker so that the hooked end of each
tool slips into the cutouts above and below the breaker. Then pry up on the top tool and down on the bottom and pull towards the front
of the chassis to unlock the barbs and free the breaker (see Figure 6).
Figure 6: Removing a breaker
Circuit Breakers
The AC Edge 240 panel is compatible with single-pole, Carling Technologies™ M-Series or AIRPAX™ SNAPAK™ series hydraulic
magnetic circuit breakers with on/off rocker positions. All circuit breakers are slow-trip without mid-trip. Transtector sells 5A and 10A
breakers under the following part numbers:
5A Carling M-Series - Transtector Part Number 3750-289
10A Carling M-Series - Transtector Part Number 3750-290
Rating
Carling Technologies™ Part Number
AIRPAX™ Sensata Part Number
1 A
MA1-X-02-234-5-A26-2-E
R15-62-1.00A-40384-1-V
2 A
MA1-X-02-234-6-A26-2-E
R15-62-2.00A-40384-2-V
3 A
MA1-X-02-234-7-A26-2-E
R15-62-3.00A-40384-3-V
4 A
MA1-X-02-234-8-A26-2-E
R15-62-4.00A-40384-4-V
5 A
MA1-X-02-227-3-A26-2-E
R15-62-5.00A-40384-5-V
10 A
MA1-X-02-227-2-A26-2-E
R15-62-10.0A-40384-10-V
Breaker Replacement