Transition Networks, Inc.
IONPS-D-R1 User Guide
33707 Rev. A
Page
34
of
50
Temperature Sensor Voltage Sensor Relay Operation Example
The example below outlines the relay operation.
Looking at Box B “Relay Enabled” in the picture above:
When “Relay Enabled “is set to False, it means the Voltage Sensor readings of the IONPS-D-R1 in slot 22
[Box A] will
not
have any effect on the Dry Contact Relay alarm indications. No alarm will ever be set
based on power supply voltage output.
When “Relay Enabled is set to True, it means the Voltage Sensor readings of the IONPS-D-R1 in slot 22
[Box A] will affect the Dry Contact Relay alarm indications. Power supply voltage output that is too high
or too low will set an alarm.
When the Relay Enabled is set to “True”, the Threshold settings show the conditions that will indicate
alarm. Those conditions are editable. Any condition showing “True” in the Last Evaluation column means an
alarm was occurring when the webpage was loaded or last refreshed.
With v 1.2.5 firmware or above, the relay operates per the table below:
ION219 with ...
IONPS-D-R1 operation with the relay's energized state = alarm:
One PS installed, in
slot 22
When power is provided to PS, it indicates no alarm.
When no power is provided to the PS, it does not indicate alarm.
One PS installed, in
slot 23
When power is provided to PS, it indicates no alarm.
When no power is provided to the PS, it does not indicate alarm.
Two PS installed:
one PS in slot 22
one PS in slot 23
When power is applied to both PS, both indicate no alarm.
When power is applied to the PS in slot 22, but not the PS on slot 23, slot 22
indicates no alarm and slot 23 indicates alarm.
When power is applied to the PS in slot 23, but not the PS on slot 22, slot 23
indicates no alarm and slot 22 indicates alarm.
When power is not supplied to either PS, both do not indicate alarm.