Reader Commands
The following table provides the commands frequently used in testing,
setting up, and tuning the Encompass 4 Reader. For a complete list of
commands see the
Encompass® 4 Reader System Guide
.
NOTE:
An “Error” reader response indicates that the command was entered
incorrectly.
Frequently Used Reader Commands
Enter
Reader Response
What It Does
#00
Done
Returns reader to data mode.
#01
Done
Switches to command mode.
#1005
Done
Set baud rate = 9600
#1010
Done
Use one stop bit
#1020
Done
Disable parity
#40
Done
Transmits all tag IDs without regard
for uniqueness
#450
Done
Disable Wiegand mode
#451
Done
Enable Wiegand mode
#454
Done
Disable multi-tag sort
#455
Done
Enable multi-tag sort
#46NN
Done
Set Wiegand retransmit interval
NN = 01–FF seconds
#48N
Done
Select tag mode
N = 0–9
0 = disable ATA
1 = enable ATA
2 = disable eGo
3 = enable eGo
4 = disable SeGo
5 = enable SeGo
6 = disable IAG
7 = enable IAG
8 = disable eATA
9 = enable eATA
NOTE
:
Encompass 4 Reader will
have tag modes specific to your
model only
#505
Model [model]
Ver [version no.] SN [serial no.]
Display version