Tests and
Troubleshooting
Displayed Failures
Static Sensor Calibration Failure
If static sensor calibration fails, the CCP uses 0.50 inch wg as the static
pressure setpoint.
The zone dampers continue to control normally. Failed static sensor
calibration may indicate that the position or location of the sensor is not
correct. See mounting the communicating sensor/bypass control in this
manual. The following conditions create a static sensor calibration failure:
• No UCMs are communicating
• No UCM can be driven to MAX due to group level overrides
• Zero static reading was not in the range of 0.15 to 0.45 Vdc
• High flow static reading is less than 0.10 Vdc greater than the zero static
reading
• Fan does not run during the start-up calibration sequence
• Design static pressure value is too low
• Bypass damper(s) are operating incorrectly
Discharge Air Temperature Sensor Failure
If the discharge air temperature sensor fails, the CCP issues a priority
shutdown command:
• All zone dampers drive to maximum
• Bypass damper drives to 50 percent
• Fan and all stages of heating and cooling are de-energized
This failure appears in diagnostics on the operator display and PC software
A shorted or open temperature sensor or failed communicating sensor/
bypass control is the cause.
Communication Failure
If communications fails (no UCMs communicating), the CCP:
• De-energizes the fan and all stages of heating and cooling
• Drives the bypass to 50 percent
Individual UCM communications failures are displayed in diagnostics on the
operator display and PC software. Check all wiring connections and polarity.
See the Communications Troubleshooting section in this manual for details.