![Trane VariTrac VAV-SVN03A-EN Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/trane/varitrac-vav-svn03a-en/varitrac-vav-svn03a-en_installation-manual_1149754023.webp)
VAV-SVN03A-EN
17
Wire AC Power
CCP Field Wiring
Field wiring to the VariTrac Central Control Panel includes:
• AC power wiring
• binary input wiring
• communication link wiring
• binary output wiring (requires optional relay board)
These procedures are detailed in the following sections. Refer to Figure 6 for
wiring connections.
Figure 6:
Field Wiring
24V
AC
V
A
CO
MM4
CO
M
M
NO
T
US
ED
P
RI
O
RI
TY
S
H
U
TD
O
W
N
OCC
/UNOC
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
24 Vac
Line voltage
Comm5
link
Comm5
link
Comm5 UCM
Tracker
Splice
2
1
4
3
3
A
A
B
B
A
A
B
B
Twisted pair, shielded wire
per Trane specifications
Shield termination
Earth ground
Contact points
Transformer
Termination resistor
Shield ground
=
=
=
=
=
=
=
Termination Board TB2
Figure note
=
Comm4
link
Comm4
link
Comm4 UCM
Comm4 UCM
Splice
-
+
-
+
+
+
-
-
Legend
Figure Notes
1 All customer wiring must be in acordance with
national, state, and local electrical codes.
2 Trane recommends a dedicated transformer
for 24 Vac power.
3 Do not apply voltage to the priority shutdown
and occupancy inputs.
4 Example of Comm5 communication link wiring.
See product-specific literature for Comm5 wire
connection details.
Wire AC Power
Содержание VariTrac VAV-SVN03A-EN
Страница 1: ...Installation Manual VariTrac Central Control Panel June 2002 VAV SVN03A EN...
Страница 52: ...VAV SVN03A EN 46 System Start Up and Checkout...
Страница 58: ...VAV SVN03A EN 52 Tests andTroubleshooting...
Страница 68: ...VAV SVN03A EN 62 Getting Started...