VAV-SVN03A-EN
27
outputs of the UCM controlling the primary damper by using the BYPS
damper cable assembly shipped with the BYPS damper.
Refer to diagram and connect as follows:
1
Disconnect the red actuator plug from the master damper UCM.
2
Plug the red actuator connector from the BYPS damper onto the master
damper UCM socket (ACT) as shown in Figure 13.
3
Reconnect the master damper actuator’s red connector to the spare
connector socket pigtailed on the BYPS damper cable assembly.
4
If cable assembly needs to be extended, cut and splice additional wire on
the BYPS damper end of the cable.
Figure 13:
Wiring for Slaved Damper
Address
Switch
DDC/UCM
Control Board
Shielded Twisted Pair
Communications Wiring
To NEC Class 2
24V Transformer
Load 8 VA (without actuator)
Female plug end of bypass
sensor assembly cable
Male plug end located on
DDC/UCM control board
DDC/UCM
Control Board
Step 3
Steps
1 & 2
Steps
1 & 2
Open
Close
Hot
Actuator
Slaved Dampers