50
CNT-SVX07D-EN
Status indicators for operation and communication
Discharge Air Temp Failure
Invalid or missing value for
discharge air temperature
Fan off
Valves closed
Outdoor air damper closed
Face and bypass damper bypass
DX cooling/electric heat off
Baseboard heat off
Automatic
Outdoor Air Temp Failure
Invalid or missing value for
outdoor air temperature
Fan unaffected
Valved unaffected
Outdoor air damper minimum
position
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Automatic
Humidity Input Failure
Invalid or missing value for
relative humidity
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Dehumidification sequence off
Automatic
CO
2
Sensor Failure
Invalid or missing value for CO
2
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Informational
Generic AIP Failure
Invalid or missing value for
generic analog input
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Informational
Local Fan Mode Failure
Invalid or missing fan-speed
switch (reverts to default fan
speed)
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Automatic
Local Setpoint Failure
Invalid or missing value for zone
temperature setpoint (reverts to
default setpoint)
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Automatic
Generic Temperature Failure
Invalid or missing generic
temperature value
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Informational
Invalid Unit Configuration
Software is configured
improperly
Fan off
Valves off
Outdoor air damper closed
Face and bypass damper closed
DX cooling/electric heat off
Baseboard heat off
Manual
Normal
On start-up
Fan unaffected
Valves unaffected
Electric heat unaffected
Compressors unaffected
Damper unaffected
Automatic
Table 16. Diagnostics (continued)
Diagnostic
Probable cause
Consequences
Diagnostic
type