Table 11. Manual output test sequence for non-face-and-bypass configurations
Step
Result
BOP1
BOP2
BOP3
BOP4
BOP5
BOP6
BOP7
BOP8
BOP9
BOP10
Number of times
Test button
is pressed
in seque
n
ce)
Fan high
1)Fan medium
2)Exhaust
Fa
n low
1)C
ool
ing/cha
n
geover
va
lv
e,
o
p
e
n
2)Two-positi
on c
ool
ing/
ch
ang
e
over va
lve
3)DX
compressor
C
ooli
n
g/
ch
a
n
geo
v
e
r
va
lv
e,
c
lo
se
1
)He
a
ti
n
g va
lv
e,
o
p
e
n
2)Two-positi
on he
at va
lve
3)Electric heat, stage 1
1
)He
a
ti
n
g va
lv
e,
c
lo
se
2)Electric heat, stage 2
Outdoor a
ir da
mper,
ope
n
Outdoor air damp
er,
cl
ose
1)Generi
c
2)Baseboa
rd heat
1
Begins test
mode
1
Off
Off
Off
Off
On/Close
Off
1) On/Close
2) Off
Off
On/Close
Off
2
Fan high
2
On/High
Off
Off
Off
Off
Off
Off
Off
Off
Off
3
Fan
medium
3
Off
1) On/Med
2) Off
Off
Off
Off
Off
Off
Off
Off
Off
4
Fan low
4
Off
Off
On/Low
Off
Off
Off
Off
Off
Off
Off
5
Main open,
DX on
On/High
Off
Off
On/Open
Off
Off
Off
Off
Off
Off
6
Main close,
DX off, aux
open, EH1
on
On/High
Off
Off
Off
On/Close
On/Open
Off
Off
Off
Off
7
Aux open,
EH1 on,
exhaust
fan
5
On/High
1) Off
2) On
Off
Off
Off
On/Open
Off
Off
Off
Off
8
Aux close,
EH1 off,
EH2 on,
damper
open
On/High
Off
Off
Off
Off
Off
On/Close
On/Open
Off
Off
9
Damper
close
On/High
Off
Off
Off
Off
Off
Off
Off
On/Close
Off
10
Generic/
baseboard
heat
energized
6
On/High
Off
Off
Off
Off
Off
Off
Off
Off
On
11: Exit
5
1
The controller turns off all fan and electric heat outputs and drives all dampers and valves closed.
2
The controller attempts to clear all diagnostics.
3
If configured for a 3-speed fan, the medium fan speed output will energize at step 3. If configured for a 2-speed fan, the fan remains on high speed at step 3.
4
If configured for a 3-speed fan, the medium fan speed output energizes at step 4. If configured for a 2-speed fan, the low fan speed output energizes at step 4. If configured
for a 1-speed fan, the fan remains on high speed at step 4.
5
If the unit is configured for a 1- or 2-speed fan, the exhaust fan output energizes on step 7. The exhaust fan output is shared with medium fan speed.
6
After step 10, the manual output test performs an exit, which initiates a reset to restore the controller to normal operation.