CNT-SVX07D-EN
11
General wiring information
Figure 3.
Connecting ac power wires to the controller
The Tracer ZN521 may be powered by an existing transformer integral to the controlled equipment,
provided the transformer has adequate power available and proper grounding is observed. If you
are providing a new transformer for power, use a UL-listed Class 2 power transformer supplying
a nominal 24 Vac (19–30 Vac). The transformer must be sized to provide adequate power to both
the Tracer ZN521 zone controller (14 VA) and its associated output devices, including relays and
actuators, to a maximum of 12 VA per output utilized.
Communication-link wiring and addressing
The Tracer ZN521 zone controller communicates with the BAS and with other LonTalk controllers
by means of a LonTalk communication link.
Important:
For important instructions on network wiring, refer to the Tracer Summit Hardware
and Software Installation guide (BMTX-SVN01A-EN).
Wiring for the communication link must meet the following requirements:
•
All wiring must comply with the National Electrical Code and local codes.
•
22 AWG Level 4 unshielded communications wire recommended for most Comm5
installations.
•
Termination resistors are required for wiring LonTalk devices communicating on a network. For
specific information about using termination resistors for LonTalk applications, refer to the
Tracer Summit Hardware and Software Installation
guide (BMTX-SVN01A-EN).
Each Tracer ZN521 zone controller has a unique 12-character alphanumeric device address for
communicating on a BAS network. This address, referred to as a
Neuron ID
, is assigned in the
factory before the product is shipped and cannot be changed. Each controller can be identified by
viewing its unique Neuron ID, which is on a printed label attached to the circuit board of the
controller. Additional adhesive-backed, peel-off Neuron ID labels are tethered to the controller for
placing on mechanical prints or unit location worksheets. The Neuron ID will appear when
communication is established with the Rover service tool or a BAS. An example Neuron ID is 00-
01-64-1C-2B-00.
24 Vac