BAS-SVX62E-EN
11
Overview
Device Connections
The following table provides information abou
t
the types of device connections.
Note:
In addition, Eight (8) expansion points can be added for XM30 or XM32 expansion modules.
Table 4.
Device connections
Connection
Quantity
Types
Range
Notes
Analog input
(AI1 to AI3)
3
Temperature
10 k
thermistor
AI1 to AI3 can be configured for timed override
capability.
Setpoint
189
to 889
Resistive
100
to 100 k
Typically used for fan speed switch.
Universal input
(UI1 and UI2)
2
Linear
0–20 mA
These inputs may be configured to be thermistor or
resistive inputs, 0–10 Vdc inputs, or 0–20 mA inputs.
Linear
0–10 Vdc
Temperature
10 k
thermistor
Setpoint
189
to 889
Resistive
100
to 100 k
Binary
Open collector/dry contact
Low impedance relay contacts recommended.
Pulse
Solid state open collector
Minimum dwell time is 25 ms On and 25 ms Off.
Binary input (BI1)
1
24 Vac detect
The UC210 controller provides the 24 Vac that is
required to drive the binary inputs when using the
recommended connections.
Binary output (BO1
to BO5)
5
TRIAC (BO2 to BO5)
0.5 A max @24 Vac, resistive and
pilot duty
Used as binary outputs and modulating 3-wire floating
point. TRIAC switches to ground.
Analog output/
binary input
(AO1/BI4 and
AO2/BI5)
2
Linear output
0–20 mA
Each termination must be configured as either an
analog output or binary input.
Linear output
0–10 Vdc
Binary input
Dry contact
PWM output
80 Hz signal @ 15 Vdc
Pressure inputs
(PI1)
1
3-wire
0–5 in H
2
O
Pressure inputs supplied with 5 volts of power.
Designed for Kavlico™ pressure transducers.
Overall Point Total
14