
64
BAS-SVX62E-EN
Troubleshooting
VAV Modulating Hot Water Failure
In the event that the heat outputs do not energize, check the following:
•
Zone temperature is at or above the heating setpoint. Increase the UC210 controller heating
setpoint.
•
Verify the valve control type selection on the TU Equipment Configuration screen. Unit needs
to be configured as modulating hot water.
•
Tracer SC has the heat output disabled. Check overrides to ensure they are not inhibiting heat
operation.
•
Heat relays have failed.
–
If the UC210 controller is calling for binary output (viewed in the Status screen), then the LED
is ON for the correct binary output to open the valve. If the TRIAC is not closed, then check
the UC210 controller TRIAC output, wiring connections, and relay output.
–
Check for correct binary outputs. It should have 24 Vac. If it does not, measure the power
input to XFMR 24 Vac input and
of the UC210 controller. The supply voltage should be
between 20.4 to 27.6 Vac (24 Vac cataloged). However, voltages at either extreme may result
in system instability.
–
Heat TRIAC(s) can be checked by purchasing a 24 Vac LED and connecting to the TRIAC
output. If they are lit, it is calling heat output to be OPEN or CLOSED by the UC210 controller.
If LED is not lit, replace the UC210 controller.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
NOTICE:
Equipment Damage!
The UC210 controller outputs are switched to ground. Do not jumper 24 Vac to binary output
TRIAC(s) because damage will occur.