TDHM AIRFLOW - COOLING
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.
0.1
0.3
0.5
0.7
0.9
CFM
723
713
699
682
661
Watts
58
109
157
204
234
CFM
773
763
747
729
707
Watts
72
125
174
222
256
CFM
823
812
795
776
753
Watts
87
141
182
241
279
CFM
873
861
842
823
798
Watts
103
158
210
260
302
CFM
923
910
892
870
844
Watts
120
177
229
279
325
CFM
998
984
964
940
912
Watts
148
206
258
309
360
CFM
1072
1058
1036
1011
981
Watts
179
238
290
341
396
CFM
1122
1107
1084
1058
1026
Watts
201
260
312
362
420
CFM
868
856
839
818
794
Watts
101
157
208
258
299
CFM
928
915
896
874
849
Watts
122
179
231
281
327
CFM
988
974
954
931
903
Watts
144
202
254
305
356
CFM
1047
1033
1012
987
958
Watts
169
227
279
330
384
CFM
1107
1092
1070
1044
1013
Watts
195
253
305
356
413
CFM
1197
1181
1157
1128
1095
Watts
237
296
346
395
455
CFM
1287
1269
1243
1213
1177
Watts
284
341
390
436
498
CFM
1347
1329
1301
1269
1232
Watts
317
373
420
465
526
CFM
1013
999
978
954
926
Watts
154
212
265
315
367
CFM
1082
1068
1048
1020
990
Watts
184
242
294
345
401
CFM
1152
1137
1113
1086
1054
Watts
215
274
325
375
434
CFM
1222
1206
1181
1152
1118
Watts
250
308
358
406
467
CFM
1292
1274
1248
1218
1182
Watts
286
344
392
439
500
CFM
1397
1378
1349
1316
1277
Watts
346
401
446
489
548
CFM
1501
1481
1451
1415
1373
Watts
411
463
503
541
595
CFM
1571
1550
1518
1481
1437
Watts
457
507
543
577
625
CFM
1157
1142
1118
1091
1058
Watts
218
276
328
377
436
CFM
1237
1220
1195
1166
1131
Watts
257
315
365
413
474
CFM
1317
1299
1272
1241
1204
Watts
300
357
405
450
512
CFM
1397
1378
1349
1316
1277
Watts
346
401
446
489
548
CFM
1476
1456
1426
1392
1350
Watts
395
448
489
529
584
CFM
1596
1575
1542
1504
1460
Watts
474
523
558
591
636
CFM
1716
1693
1658
1617
1569
Watts
560
604
631
726
726
CFM
1796
1771
1735
1693
1642
Watts
622
661
682
726
726
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
External Static Pressure
290 CFM/ton
*DHMC100ACV4VB^
Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
310 CFM/ton
330 CFM/ton
Unit
Outdoor
Airflow
Setting
450 CFM/ton
3
290 CFM/ton
310 CFM/ton
330 CFM/ton
2.5
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
430 CFM/ton
450 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
3.5
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
450 CFM/ton
C
ooling
4
290 CFM/ton
310 CFM/ton
430 CFM/ton
450 CFM/ton
370 CFM/ton
400 CFM/ton
330 CFM/ton
350 CFM/ton