13
Pub. No. 22-1840-14
TUHM AIRFLOW - COOLING
0.1
0.3
0.5
0.7
0.9
CFM
1000
1024
1028
1022
1011
Watts
122
168
209
251
300
CFM
1072
1094
1097
1089
1076
Watts
140
188
234
281
331
CFM
1143
1164
1165
1157
1141
Watts
160
211
261
313
364
CFM
1214
1233
1234
1224
1207
Watts
182
236
291
347
400
CFM
1286
1303
1302
1291
1272
Watts
207
264
323
384
438
CFM
1393
1408
1405
1392
1370
Watts
250
311
377
444
500
CFM
1500
1513
1508
1492
1468
Watts
300
365
437
509
565
CFM
1571
1582
1576
1559
1533
Watts
337
406
481
555
611
CFM
1148
1169
1170
1161
1146
Watts
161
213
263
315
367
CFM
1230
1248
1248
1238
1221
Watts
187
242
297
355
408
CFM
1311
1328
1327
1315
1295
Watts
217
274
335
398
452
CFM
1393
1408
1405
1392
1370
Watts
250
311
377
444
500
CFM
1474
1488
1483
1468
1445
Watts
287
352
422
493
549
CFM
1597
1607
1601
1583
1556
Watts
352
421
497
572
628
CFM
1719
1727
1718
1699
1668
Watts
427
503
581
655
711
CFM
1801
1807
1797
1775
1743
Watts
483
563
642
712
768
CFM
1444
1458
1454
1440
1417
Watts
273
336
405
475
530
CFM
1546
1557
1552
1535
1510
Watts
324
391
465
538
594
CFM
1648
1657
1650
1631
1603
Watts
381
454
531
606
662
CFM
1750
1757
1748
1727
1696
Watts
447
525
603
676
732
CFM
1852
1857
1845
1823
1790
Watts
522
604
682
749
804
CFM
2004
2006
1992
1967
1947
Watts
651
742
811
863
966
CFM
2157
2156
2140
2050
1947
Watts
803
902
966
966
966
CFM
2259
2255
2140
2050
1947
Watts
966
966
966
966
966
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
450 CFM/ton
370 CFM/ton
400 CFM/ton
350 CFM/ton
370 CFM/ton
450 CFM/ton
C
ool
ing
430 CFM/ton
370 CFM/ton
400 CFM/ton
5
4
290 CFM/ton
310 CFM/ton
330 CFM/ton
430 CFM/ton
450 CFM/ton
350 CFM/ton
*UHMD120ACV5VB^
Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
Airflow
Setting
External Static Pressure
3.5
290 CFM/ton
Unit
Outdoor
310 CFM/ton
330 CFM/ton
400 CFM/ton
430 CFM/ton
NOTE:
CONTINUOUS fan mode during
COOLING operation may not be
appropriate in humid climates. If the
indoor air exceeds 60% relative humidity
or simply feels uncomfortably humid,
it is recommended that the fan only be
used in the AUTO mode.