background image

8

Initial Power-Up

Before applying power to the unit, verify that all wiring is
correct.

When the power to the unit has been turned “On”, the ZSM
will be in the Normal Run State and will begin operating us-
ing the factory default settings. The correct day and time
settings will need to be verified or set.  Refer to the Normal
Run State screen.

To set the time, simply press the (“+”) or (“-“) side of the
KEY marked TIME.  Press the positive (“+”) side to advance
the time in one minute intervals. Press the negative (“-“)
side to decrease the time in one minute intervals. Press and
hold either side of the KEY to make rapid changes.

When the correct time is reached, release the TIME KEY
and the time will be set.

To set the day, simply press the DAY KEY until the correct
day is displayed.

Programming And Operation

Содержание SENS-IN-1D18-HD60D29-4

Страница 1: ...BAYSENS019B 2 25 T Packaged Heat Cool Units ASYSTAT666B 2 20 T Packaged Heat Pump Units 27 5 50 T Packaged Heat Cool Units 20 130 T Packaged Rooftop Units 20 80 T Commercial Self Contained Units PROG...

Страница 2: ...ships inside each Programmable Zone Sensor kit and is customer property The unit s maintenance personnel must retain it This booklet describes step by step instructions for install ing and programmin...

Страница 3: ...ENS019B This 7 day programmable sensor features 2 3 or 4 periods for Occupied or Unoccupied programming per day If the power is interrupted the program is retained in permanent memory If power is off...

Страница 4: ...4 General Information...

Страница 5: ...in place and mark the three holes Drill three 3 16 inch 4 8 mm holes Gently tap the plastic anchors into the holes until they are flush with the wall Level the sub base and firmly tighten the mounting...

Страница 6: ...E SERVICING Failure to disconnect power before servicing can cause severe personal injury or death Connecting the wires 1 Strip approximately inch of insulation from each wire and connect the wiring t...

Страница 7: ...7 Installation Figure 3 Zone Sensor Connection Diagram...

Страница 8: ...ied or set Refer to the Normal Run State screen To set the time simply press the or side of the KEY marked TIME Press the positive side to advance the time in one minute intervals Press the negative s...

Страница 9: ...enu Pressing the TIME and KEY changes the option value associated with each option number Refer to the Option Menu Screen illustration and the ZSM options and option values table with a description of...

Страница 10: ...ammed If 4 is selected Morn Day Eve and Nite can be programmed 10 Programmable Fan Operation 0 Disallowed 1 Allowed 0 If allowed Supply Fan operation can be programmed for On or Auto operation for eac...

Страница 11: ...OCCUPIED 8 Press the FAN KEY to program the fan to be either ON or AUTO for this period Note This feature will not be available if option 10 in the OPTIONS MENU has been set to 0 9 Pressing the ERASE...

Страница 12: ...12 Programming And Operation...

Страница 13: ...Cool Set Point Occupied Unoccupied Morn Occ Unocc Day Occ Unocc Eve Occ Unocc Nite Occ Unocc Friday Start Time Heat Set Point Cool Set Point Occupied Unoccupied Morn Occ Unocc Day Occ Unocc Eve Occ U...

Страница 14: ...r of days 4 Press the UP or DOWN arrows to program the tem perature set points HEAT and or COOL Use the MODE KEY to toggle between the Modes if applicable 5 Press the FAN KEY to program the fan for ON...

Страница 15: ...15 Programming And Operation...

Страница 16: ...16 Programming And Operation...

Страница 17: ...rminal 8 COOL Icon ON Indicates by a continuously illuminated icon that the unit is operating in the Cooling Mode FLASHING The COOL FAILURE icon indicates that a system failure in the Cooling Mode has...

Страница 18: ...ndition 2 If Option 11 in the Options Menu is set to 0 then the local thermistor is selected and the on board thermistor is open and rhe ZSM must be replaced Zone Temperature is not displayed Verify t...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: