background image

6

Installation

UCM Status Inputs (4 Wires Optional)
The ZSM can be wired to receive four (4) operating status
signals from the UCM (HEAT, COOL, SYSTEM “ON”, SER-
VICE). Four (4) wires from the UCM should be connected to
the appropriate terminals (7, 8, 9 & 10) on the ZSM.

Auxiliary Relay (3 Wires Optional)
The auxiliary relay located on the ZSM is energized during
OCCUPIED periods. The auxiliary relay is form C, rated for
1.25 Amps at 30 VAC. Figure 3 illustrates the terminal con-
figuration.

Note: Guidelines for wire sizes and lengths are
shown in Table 1. The total resistance of these low
voltage wires must not exceed 2.5 ohms per
conductor. Any resistance greater than 2.5 ohms
may cause the control to malfunction due to
excessive voltage drop.

Note: Do not run low-voltage control wiring in same
conduit with high-voltage power wiring.

Table 1

Zone Sensor Maximum Lengths and Wire Size

Distance from

Recommended

Unit to Control

Wire Size

000 - 150 feet

22 gauge

151 - 240 feet

20 gauge

241 - 385 feet

18 gauge

386 - 610 feet

16 gauge

611 - 970 feet

14 gauge

Wiring The Sub Base

H A Z A R D O U S   V O L T A G E !

DISCONNECT ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE SERVICING.

Failure to disconnect power before servicing can
cause severe personal injury or death.

 

Connecting the wires

1. Strip approximately ¼ inch of insulation from each wire

and connect the wiring to the appropriate 

terminals at

the unit control panel.

2. Remove the Terminal Block from the hardware package

and 

connect the wiring to the appropriate 

terminals at

the Zone 

Sensor sub base. In general, zone sensor

connections use the convention of connecting Zone
Sensor terminals to like numbered Unit terminals (1 to
1, 2 to 2, etc.). Refer to Figure 3.

3. Firmly tighten each screw terminal.

4. Attach the terminal block to the Sensor PC Board.

5. Fit the wires as close to the sub base as possible.  Be

sure to push the excess wire into the wall and plug the
hole with nonflammable insulation to prevent drafts
from affecting the sensor.

Note: Do Not Coil Excess Wire Inside Sub Base!
Push All Excess Wire Inside Handy Box Or Inside
Wall Cavity.

6.  Replace cover. Place the zone sensor on the sub base

by hooking the top two tabs on the Zone Sensor Module
to the slotted tabs on top of the sub base.  Swing the
ZSM straight down onto the sub base until you hear the
plastic locking mechanism snap securely into place.

Note: If the wire bundle is large, it may cause the
terminal strip to become disconnected. Secure the
wires to the sub base using a small wire tie.

Содержание SENS-IN-1D18-HD60D29-4

Страница 1: ...BAYSENS019B 2 25 T Packaged Heat Cool Units ASYSTAT666B 2 20 T Packaged Heat Pump Units 27 5 50 T Packaged Heat Cool Units 20 130 T Packaged Rooftop Units 20 80 T Commercial Self Contained Units PROG...

Страница 2: ...ships inside each Programmable Zone Sensor kit and is customer property The unit s maintenance personnel must retain it This booklet describes step by step instructions for install ing and programmin...

Страница 3: ...ENS019B This 7 day programmable sensor features 2 3 or 4 periods for Occupied or Unoccupied programming per day If the power is interrupted the program is retained in permanent memory If power is off...

Страница 4: ...4 General Information...

Страница 5: ...in place and mark the three holes Drill three 3 16 inch 4 8 mm holes Gently tap the plastic anchors into the holes until they are flush with the wall Level the sub base and firmly tighten the mounting...

Страница 6: ...E SERVICING Failure to disconnect power before servicing can cause severe personal injury or death Connecting the wires 1 Strip approximately inch of insulation from each wire and connect the wiring t...

Страница 7: ...7 Installation Figure 3 Zone Sensor Connection Diagram...

Страница 8: ...ied or set Refer to the Normal Run State screen To set the time simply press the or side of the KEY marked TIME Press the positive side to advance the time in one minute intervals Press the negative s...

Страница 9: ...enu Pressing the TIME and KEY changes the option value associated with each option number Refer to the Option Menu Screen illustration and the ZSM options and option values table with a description of...

Страница 10: ...ammed If 4 is selected Morn Day Eve and Nite can be programmed 10 Programmable Fan Operation 0 Disallowed 1 Allowed 0 If allowed Supply Fan operation can be programmed for On or Auto operation for eac...

Страница 11: ...OCCUPIED 8 Press the FAN KEY to program the fan to be either ON or AUTO for this period Note This feature will not be available if option 10 in the OPTIONS MENU has been set to 0 9 Pressing the ERASE...

Страница 12: ...12 Programming And Operation...

Страница 13: ...Cool Set Point Occupied Unoccupied Morn Occ Unocc Day Occ Unocc Eve Occ Unocc Nite Occ Unocc Friday Start Time Heat Set Point Cool Set Point Occupied Unoccupied Morn Occ Unocc Day Occ Unocc Eve Occ U...

Страница 14: ...r of days 4 Press the UP or DOWN arrows to program the tem perature set points HEAT and or COOL Use the MODE KEY to toggle between the Modes if applicable 5 Press the FAN KEY to program the fan for ON...

Страница 15: ...15 Programming And Operation...

Страница 16: ...16 Programming And Operation...

Страница 17: ...rminal 8 COOL Icon ON Indicates by a continuously illuminated icon that the unit is operating in the Cooling Mode FLASHING The COOL FAILURE icon indicates that a system failure in the Cooling Mode has...

Страница 18: ...ndition 2 If Option 11 in the Options Menu is set to 0 then the local thermistor is selected and the on board thermistor is open and rhe ZSM must be replaced Zone Temperature is not displayed Verify t...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: