background image

18

Troubleshooting

Problem

Solution

Display does not come on.

Check the 24 VAC power supply at terminals 11 and 14 at the Zone Sensor.  
Verify that the terminal block is properly positioned on its pins.

No communications to the UCP.

Check for 22 to 42 VDC between terminals 11 and 12 at the Zone Sensor.  
Check wiring if no voltage is present.

Dispalyed Zone Temperature reads 
Sh and the COOL FAIL icon is 
continuiously illuminated.

1.  Verify that Option 11 in the Options Menu is set correctly.  If correct, check 
the wiring from the remote sensor at terminals S1 and S2 for a shcrted 
condition.

2.  If Option 11 in the Options Menu is set to 0, then the local thermistor is 
selected and the on-board thermistor is shorted and the ZSM must be replaced.

Dispalyed Zone Temperature reads 
oP and the COOL FAIL icon is 
continuiously illuminated.

1.  Verify that Option 11 in the Options Menu is set correctly.  If correct, check 
the wiring from the remote sensor at terminals S1 and S2 for a open circuit 
condition.

2.  If Option 11 in the Options Menu is set to 0, then the local thermistor is 
selected and the on-board thermistor is open and rhe ZSM must be replaced.

Zone Temperature is not displayed.

Verify that number 1 has been selected for option 13 in the Options Menu.

ZSM keypad does not respond to 
selection

Verify that the Keypad is not in the Lockout Mode.  Press and hold the TIME ("+") 
and ("-") Key for 4 seconds to unlock the keypad.

The Clock requires reprogramming 
after short power interruptions.

Replace Battery.

FAN Mode is set in the ON position 
but the Fan is not running.

Check option 6 in the Options Menu.  Refer to the Options Menu section for 
option description.

System is operating before the 
programmed start time.

Check option 7 in the Options Menu.  Computed recovery option overrides the 
last part of an unoccupied period to obtain the occupied setting in time.

Buzzer indicates System Failure or 
Service is required.

Press the ERASE Key to reset the filter lapse timer.  Buzzer will be reset until 
noon of the next day if a System Failure has not been corrected.

Note: To reset the program and initiate a Self Diagnostic Test; press the PROGRAM KEY, HOLD TEMP KEY, and DAY KEY

         simultaniously.

Содержание SENS-IN-1D18-HD60D29-4

Страница 1: ...BAYSENS019B 2 25 T Packaged Heat Cool Units ASYSTAT666B 2 20 T Packaged Heat Pump Units 27 5 50 T Packaged Heat Cool Units 20 130 T Packaged Rooftop Units 20 80 T Commercial Self Contained Units PROG...

Страница 2: ...ships inside each Programmable Zone Sensor kit and is customer property The unit s maintenance personnel must retain it This booklet describes step by step instructions for install ing and programmin...

Страница 3: ...ENS019B This 7 day programmable sensor features 2 3 or 4 periods for Occupied or Unoccupied programming per day If the power is interrupted the program is retained in permanent memory If power is off...

Страница 4: ...4 General Information...

Страница 5: ...in place and mark the three holes Drill three 3 16 inch 4 8 mm holes Gently tap the plastic anchors into the holes until they are flush with the wall Level the sub base and firmly tighten the mounting...

Страница 6: ...E SERVICING Failure to disconnect power before servicing can cause severe personal injury or death Connecting the wires 1 Strip approximately inch of insulation from each wire and connect the wiring t...

Страница 7: ...7 Installation Figure 3 Zone Sensor Connection Diagram...

Страница 8: ...ied or set Refer to the Normal Run State screen To set the time simply press the or side of the KEY marked TIME Press the positive side to advance the time in one minute intervals Press the negative s...

Страница 9: ...enu Pressing the TIME and KEY changes the option value associated with each option number Refer to the Option Menu Screen illustration and the ZSM options and option values table with a description of...

Страница 10: ...ammed If 4 is selected Morn Day Eve and Nite can be programmed 10 Programmable Fan Operation 0 Disallowed 1 Allowed 0 If allowed Supply Fan operation can be programmed for On or Auto operation for eac...

Страница 11: ...OCCUPIED 8 Press the FAN KEY to program the fan to be either ON or AUTO for this period Note This feature will not be available if option 10 in the OPTIONS MENU has been set to 0 9 Pressing the ERASE...

Страница 12: ...12 Programming And Operation...

Страница 13: ...Cool Set Point Occupied Unoccupied Morn Occ Unocc Day Occ Unocc Eve Occ Unocc Nite Occ Unocc Friday Start Time Heat Set Point Cool Set Point Occupied Unoccupied Morn Occ Unocc Day Occ Unocc Eve Occ U...

Страница 14: ...r of days 4 Press the UP or DOWN arrows to program the tem perature set points HEAT and or COOL Use the MODE KEY to toggle between the Modes if applicable 5 Press the FAN KEY to program the fan for ON...

Страница 15: ...15 Programming And Operation...

Страница 16: ...16 Programming And Operation...

Страница 17: ...rminal 8 COOL Icon ON Indicates by a continuously illuminated icon that the unit is operating in the Cooling Mode FLASHING The COOL FAILURE icon indicates that a system failure in the Cooling Mode has...

Страница 18: ...ndition 2 If Option 11 in the Options Menu is set to 0 then the local thermistor is selected and the on board thermistor is open and rhe ZSM must be replaced Zone Temperature is not displayed Verify t...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: