Diagnostics
80
PKG-SVX027A-EN
Condenser Water Entering Temperature (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
Only affects the Water Side
Economizer, if installed,
from operating until this
sensor is in a Normal State.
The Pressure sensor is
reading either above is
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• Sensor has Failed. Verify if
sensor has any resistance
on it, should be 8-12k of
resistance on the
thermistor.
None, alarm clears once
sensor is in a normal state.
Condenser Water Leaving Temperature (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
Only affects the Water Side
Economizer, if installed,
from operating until this
sensor is in a Normal State.
The Pressure sensor is
reading either above is
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• Sensor has Failed. Verify if
sensor has any resistance
on it, should be 8-12k of
resistance on the
thermistor.
None, alarm clears once
sensor is in a normal state.
Condenser Tee Strainer High Pressure (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Service Required.
Affects the alarm for Dirty
Strainer, preventing alarm
from working properly.
The Pressure sensor is
reading either above is
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• Sensor has Failed. Verify if
sensor has any resistance
on it, should be 8-12k of
resistance on the
thermistor.
None, alarm clears once
sensor is in a normal state.
Table 32. General unit warning (continued)