Diagnostics
PKG-SVX027A-EN
77
Table 31. General unit alarming
Emergency Stop (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from operating
until the sensor is in a
normal state.
The emergency stop input
has an open condition which
indicates an emergency stop
command.
• Emergency Stop Binary
Input is open.
Manual reset required once
the issue is resolved. User
must toggle the alarm reset
value.
External Auto/Stop (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from operating
until the sensor is in a
normal state.
Theexternal auto/stop input
has an open condition which
indicates an emergency stop
command.
• Emergency stop binary
input is open.
None, alarm clears once
sensor is in a normal state.
Local Auto/Stop (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from operating
until the sensor is in a
normal state.
The local auto/stop value
has been commanded to the
local stop command.
• Emergency stop binary
input is open.
None, alarm clears once
sensor is in a normal state.
Discharge Air Temperature (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Unit will shut down and be
prevented from running
until this sensor is in a
normal state.
The temperature sensor is
reading either above is
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• Sensor has Failed. Verify if
sensor has any resistance
on it, should be 8-12k of
resistance on the
thermistor.
None, alarm clears once
sensor is in a normal state.