Diagnostics
PKG-SVX027A-EN
75
Diagnostic: Compressor (1-4) Low Superheat (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this diagnostic
is cleared.
The Calculated superheat is
below 4 degrees for 5
minutes.
• Over Charge on unit.
• Malfunctioning TXV.
• Dirty Condenser tubes.
• Too little across the
evaporator
Manual Reset Required once
the issue is resolved. User
must toggle the Compressor
(1-4) Failure Reset
Diagnostic: Compressor 1 Safety Circuit Alarm (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this diagnostic
is cleared.
The Compressor VFD has
indicated that it’s in fault or
the Compressor is
commanded on but does not
indicate status.
• VFD has an issue
• Relay starting compressor is
malfunctioning.
• XM Module commanding
compressor relay is failed or
not communicating.
Manual Reset Required once
the issue is resolved. User
must toggle the Compressor
1 Failure Reset
Diagnostic: Compressor (2-4) Safety Circuit Alarm (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this diagnostic
is cleared.
The Compressor Protection
module has indicated an
alarm or the Compressor is
commanded on but does not
indicate status.
• VFD has an issue
• Relay starting compressor is
malfunctioning.
• XM Module commanding
compressor relay is failed or
not communicating.
Manual Reset Required once
the issue is resolved. User
must toggle the Compressor
1 Failure Reset
Note:
These Alarms will effect the operation of the compressor.
Table 28. Compressor alarming (continued)
Table 29. Compressor warning
Warning: Compressor 1 Cond Limit Status (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Warning.
Compressor speed will be
limited to keep the
compressor from exceeding
the Condenser Control
Pressure Setpoint.
Head Pressure has exceeded
the condenser Control
Pressure Setpoint.
• High Condenser Water
Temperature
• Malfunctioning TXV.
• Non Condensable in the
refrigerant.
• Low water flow in the
condenser, or no water flow.
• Condenser Valve
malfunctioning.
No Reset required, Warning
clears when conditions no
longer exists.