Controls
PKG-SVX027A-EN
51
XM30.9
AO1/UI1
Compressor 2 Discharge Pressure Sensor Local
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO2/UI2
Compressor 2 Suction Pressure
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO3/UI3
Compressor 2 Suction Temperature
10K Ohm Resistor Trane Type 2
AO4/UI4
Compressor 2 Condenser Regulating Valve
2VDC = 0% Open, 10VDC = 100% Open
XM30.10
AO1/UI1
Compressor 3 Discharge Pressure Sensor Local
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO2/UI2
Compressor 3 Suction Pressure
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO3/UI3
Compressor 3 Suction Temperature
10K Ohm Resistor Trane Type 2
AO4/UI4
Compressor 3 Condenser Regulating Valve
2VDC = 0% Open, 10VDC = 100% Open
XM30.11
AO1/UI1
Compressor 4 Discharge Pressure Sensor Local
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO2/UI2
Compressor 4 Suction Pressure
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
AO3/UI3
Compressor 4 Suction Temperature
10K Ohm Resistor Trane Type 2
AO4/UI4
Compressor 4 Condenser Regulating Valve
2VDC = 0 % Open, 10VDC = 100% Open
XM32.12
BO1
Cooling Tower/Pump Request
NO Open = Request for Off, NO Closed = Request for On;
NC Not Used
BO2
Unit Alarm Output Command
NO Open = No Alarm, NO Closed = Alarm;NC not used
BO3
VAV Box Drive Open Command
NO Open = Normal Operation, NO Closed = Drive Max
Valve Position; NC Not used
BO4
Comp 1 VFD E-Stop Alarm Contact
NO Open = Normal, NO Closed = Emergency Stop, NC
Not used
XM32.13
BO1
Dirty Filter Alarm
NO Open = Normal, NO Closed = Alarm; NC Not used
BO2
Refrigeration Circuit Failure Alarm
Open = Normal, Closed = Alarm
BO3
Supply Fan Failure Alarm
Open = Normal, Closed = Alarm
BO4
Heat Failure Alarm
Open = Normal, Closed = Alarm
XM30.14
AO1/UI1
Occupied Zone Cool Setpoint
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
AO2/UI2
Occupied Zone Heat Setpoint
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
AO3/UI3
Unoccupied Zone Cool Setpoint
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
AO4/UI4
Unoccupied Zone Heat Setpoint
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
XM30.15
AO1/UI1
Supply Air Cooling Setpoint
0.5VDC = 40 Deg F, 4.5VDC = 90 Deg F
AO2/UI2
Supply Air Heating Setpoint
0.5VDC = 40 Deg F, 4.5VDC = 90 Deg F
AO3/UI3
Supply Air Static Pressure Setpoint
0.5VDC = 0 In WC, 4.5VDC = 5 In WC
AO4/UI4
Demand Limit Input
Open = Normal, Closed = 50% Reduction
NO = Normally Open, NC = Normally Closed
Table 23. Points list (continued)
Hardware
Connection
Point Name
Point Setup