Diagnostics
72
PKG-SVX027A-EN
Table 28. Compressor alarming
Diagnostic: Compressor (1-4) Discharge Pressure Sensor Failure (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this diagnostic
is cleared.
The Pressure sensor is
calculated to be in fault and
the unit has locked out the
compressor from operation.
• Sensor has lost its 5VDC
Source Signal. Verify that
the sensor has 5 VDC.
• Sensor is not wired
properly: Verify wiring to the
XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• System has no charge:
Verify that the system has a
refrigerant charge.
• Sensor has Failed.
Manual Reset Required once
the sensor is in a Normal
State. User must toggle the
Compressor (1-4) Failure
Reset
Compressor (1-4) Discharge Pressure Sensor Failure (In Fault)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this sensor is in
a normal state.
The Pressure sensor is
reading either Above or
Below its minimum value,
resulting in a Fault Condition
after 3 point updates.
• Sensor has lost its 5VDC
Source Signal. Verify that
the sensor has 5 VDC.
• Sensor is not wired
properly: Verify wiring to the
XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• System has no charge:
Verify that the system has a
refrigerant charge.
• Sensor has Failed.
None, fault clears once
sensor is in a normal state.
Diagnostic: Compressor (1-4) Suction Pressure Sensor Failure (In Alarm)
Notification Class
Action
Reason
Typical Causes
Reset Required
HVAC Critical Alarm.
Compressor will be locked
out and prevented from
running until this diagnostic
is cleared.
The Pressure sensor is
calculated to be in fault and
the unit has locked out the
compressor from operation.
• Sensor has lost its 5VDC
Source Signal. Verify that
the sensor has 5 VDC.
• Sensor is not wired
properly: Verify wiring to the
XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
talking to the UC600.
• System has no charge:
Verify that the system has a
refrigerant charge.
• Sensor has Failed.
Manual Reset Required once
the sensor is in a Normal
State. User must toggle the
Compressor (1-4) Failure
Reset.