18

PKG-SVX14A-EN

mechanical

requirements

Installation

Refrigerant Piping (Air-Cooled

Units Only)

Reference industry recommendations

for air-cooled unit refrigerant piping. If

suspending piping from the building, use

isolation hangers to prevent vibration

transmission.
Air-cooled units ship with a holding

charge of nitrogen. Before installing unit

piping, momentarily depress either the

suction or discharge line access valve to

verify that the holding charge has not

been lost. If  nitrogen does not escape

when depressing the access valve, leak-

test the entire refrigerant system to

determine the source of loss.
The charge is contained by a continuous

loop of both hot gas and liquid lines. You

must cut the loop for connection to

discharge and liquid lines. See Figure  I-

MR-1.

Brazing Procedures

Proper brazing techniques are essential

when installing refrigerant piping. Keep

the following factors in mind when

making sweat connections.

1. When heating copper in the presence

of air, copper oxide forms. To prevent

copper oxide from forming inside the

tubing during brazing, sweep an inert

gas, such as dry nitrogen, through the

tubing. Nitrogen displaces air in the

tubing and prevents oxidation of

interior surfaces. A nitrogen flow of one

to three cubic feet per minute is

sufficient to displace the air. Use a

pressure regulating valve or flow meter

to control the flow.

2. Ensure  tubing surfaces that require

brazing are clean and the ends of the

tubes are carefully reamed to remove

any burrs.

3. Make sure the inner and outer tubes of

the joint are symmetrical and have a

close clearance, providing an easy slip

fit. If the joint is too loose, the tensile

strength of the connection will be

significantly reduced. Make the overlap

distance equal to the inner tube

diameter.

4. Wrap the body of each refrigerant line

component with a wet cloth to keep it

cool during brazing. Excessive heat can

damage the components.

5. If using flux, apply it sparingly to the

joint. Excess flux will contaminate the

refrigerant system.

6. Apply heat evenly over the length and

circumference of the joint, making sure

the entire joint becomes hot enough to

melt the brazing material.

7. Begin brazing when the joint is hot

enough to melt the brazing rod. The hot

copper tubing, not the flame, should

melt the rod.

8. Continue to apply heat around the joint

circumference until the brazing material

is drawn into the joint by capillary

action, making a mechanically sound

and gas-tight connection.

9. Visually inspect the connection after

brazing to locate any pin holes or

crevices in the joint. Use a mirror to

inspect connections that are difficult to

see.

Figure  I-MR-1.  Air-cooled  unit  refrigerant  piping

WARNING:

Hazard of Explosion and Deadly 

Gases!

 

Never solder, braze or weld on 

refrigerant lines or any unit com-

ponents that are above atmo-

spheric pressure or where 

refrigerant may be present. 

Always remove refrigerant by fol-

lowing the guidelines estab-

lished by the EPA Federal Clean 

Air Act or other state or local 

codes as appropriate. After refrig-

erant removal, use dry nitrogen to 

bring system back to atmospheric 

pressure before opening system 
for repairs. Mixtures of refriger-

ants and air under pressure may 

become combustible in the pres-

ence of an ignition source leading 

to an explosion. Excessive heat 

from soldering, brazing or weld-

ing with refrigerant vapors 

present can form highly toxic 

gases and extremely corrosive 

acids. Failure to follow all proper 

safe refrigerant handling prac-

tices could result in death or seri-

ous injury.

Electrical Requirements

Follow these guidelines, referring to unit

wiring diagrams and supply power

dimensional information to ensure

correct electrical requirements at the

installation site. Reference supply power

wiring locations on unit submittals orin

the “Dimensions and Weights” section.

Specific unit wiring diagrams are

provided on each unit. Use these

diagrams for connections or trouble

analysis.

Unit Wiring Diagrams

Specific unit wiring diagrams are

provided on the inside of the control

panel door. Use these diagrams for

connections or trouble analysis.

Содержание SCRH

Страница 1: ...PKG SVX14A EN Installation Operation and Maintenance Midrange Self Contained Units October 2008 Models SCWH SCRH 3 5 7 5 10 12 15 tons AO and later design sequence...

Страница 2: ...ous Voltage Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure power cannot be inadvertently energized Failure to disconnect...

Страница 3: ...tion 2 pre installation considerations 6 dimensions weights 11 mechanical requirements 17 electrical requirements 19 installation procedure 21 pre startup requirements 22 startup 23 Operation 24 seque...

Страница 4: ...igit 8 unit voltage 3 208 230 volt 60 hz 3 ph 4 460 volt 60 hz 3 ph 5 575 volt 60 hz 3 ph Digit 9 air flow configuration 2 vertical discharge front return 3 vertical discharge rear return Digit 10 11...

Страница 5: ...efrigerant quality standards are addressed in ARI Standard 700 Refrigerant Handling and Safety Consult the manufacturer s material safety data sheet MSDS for information on refrigerant handling to ful...

Страница 6: ...hin the allotted time after delivery Check with the carrier for their allotted time to submit a claim Do not move damaged material from the receiving location It is the receiver s responsibility to pr...

Страница 7: ...MPRESSOR ACCESS 42 SERVICE CLEARANCE FRONT DRAIN CONNECTION AIR FILTER ACCESS BOTH SIDES BOTH SIDES 26 SERVICE CLEARANCE LEFT SIDE SIGHT GLASS FILTER DRIER ACCESS RIGHT SIDE 24 26 SERVICE CLEARANCE LE...

Страница 8: ...8 PKG SVX14A EN Installation pre installation considerations Service Access 10 12 15 ton SCWH SRCH with side mounted fan configura tion field converted 10 through 15 ton SCRH SCWH...

Страница 9: ...r cooled models water cooled models L1 L2 L3 L4 L1 L2 L3 L4 10 tonunit 318 150 363 169 383 211 383 211 spring red yellow red yellow red yellow red yellow rubber in shear green red green red green red...

Страница 10: ...ase Protect the unit from damage by rigging equipment WARNING Improper Unit Lift Test lift unit approximately 24 inches high to verify the proper center of gravity lift point To avoid dropping the uni...

Страница 11: ...erted SCWH SCRH dimensions weight in lbs unit shipping operating size A B C D E F G J K L M N O P Q R S weight weight 3 31 89 64 17 22 24 5 65 11 93 14 31 10 63 18 00 7 80 7 80 15 60 15 63 20 20 6 28...

Страница 12: ...KG SVX14A EN dimensions weights 7 5 tons SCWH SCRH Installation SCWH vertical discharge horizontal discharge field converted SCWH SCRHweight lbs unit shipping operating size weight weight 7 5 702 657...

Страница 13: ...vertical discharge SCRH SCWH SCWH SCRH dimensions weight in lbs unit shipping operating tons A B C D E F G J K M N weight weight 10 66 75 88 78 7 04 18 07 57 28 19 01 25 0 5 23 7 48 5 8 8 30 984 917 1...

Страница 14: ...7 04 18 07 57 28 66 93 25 79 12 65 75 7 04 18 07 61 22 66 93 29 73 15 80 31 19 83 19 83 61 22 81 49 29 73 Notes 1 Base rail must be attached to the floor before converting unit to side mounted fan co...

Страница 15: ...ton 65 75 29 52 120 15 ton 80 31 29 52 146 A B C D E F G 0 39 0 28 1 38 1 38 5 91 1 57 3 15 0 39 0 59 0 59 2 18 2 18 8 39 1 03 1 03 1 08 0 75 0 75 5 9 1 0 NPT Hot water coil 3 5 ton units SCWH SCRH H...

Страница 16: ...LED Hot water coil 10 thru 15 ton units 35 51 28 03 5 91 0 43 1 57 3 15 34 72 0 39 0 75 0 75 0 39 5 9 1 0 NPT 0 75 17 00 0 75 2 22 2 22 16 25 20 7 0 39 1 87 8 48 8 48 14 64 1 55 1 55 3 03 0 39 1 87 1...

Страница 17: ...1 Remove back panel to access the water connection fittings 2 Attach the water supply line to the inlet connection and the return line to the outlet connection The water connection fittings are copper...

Страница 18: ...ly to the joint Excess flux will contaminate the refrigerant system 6 Apply heat evenly over the length and circumference of the joint making sure the entire joint becomes hot enough to melt the brazi...

Страница 19: ...e voltage at the compressor terminals to determine if it is balanced Voltage imbalance on three phase systems can cause motor overheating and premature failure The maximum allowable imbalance is 2 0 V...

Страница 20: ...460V 60Hz 3Ph 13 6 100 0 4 60 35 2 45 6 18 36 8 50 SC H1505 575V 60Hz 3Ph 10 9 78 0 3 40 27 9 35 4 94 29 5 35 12 2 tons MFS MCB model voltage compressor evap fan motor min circuit ampacity 10 2 2 1 2...

Страница 21: ...field wiring connections Note All field installed wiring must comply with NEC and applicable local codes Fan Discharge Conversion Complete the steps below to convert the fan discharge from vertical t...

Страница 22: ...ements Check unit for missing material Look for ship with accessories that are packaged separately and placed inside the access panel fan section or compressor section See the Receiving and Handling s...

Страница 23: ...n and check for unusual noise vibration belt and fan clearances WARNING Hazardous voltage Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout proce...

Страница 24: ...ects power from the thermostat contacts that control the condensing unit This prevents the condensing unit from running regardless of the thermostat tempera ture setting The evaporator fan may circula...

Страница 25: ...83 indoor coil 3 8 tube size face area sq ft 3 19 4 98 7 13 12 12 12 12 14 56 rows fpf 4 144 4 144 3 168 2 168 2 168 3 168 water condenser tube tube water connection in 3 4 NPT 3 4 NPT 3 4 NPT 1 1 4 N...

Страница 26: ...rsonal safety refer to the cleaning agent manufacturer s materials safety data sheet and follow all recommended safe handling practices Failure to follow all safety instructions could result in death...

Страница 27: ...ecovering and condensing refrigerant into containment When leak checking with trace refrigerant and nitrogen use HCFC22 R22 rather than CFC12 R12 or any other fully halogenated refrigerants Be aware o...

Страница 28: ...rkover may cause damage to the motor windings WARNING Hazardous Pressures If a heat source is required to raise the tank pressure during removal of refrigerant from cylinders use only warm water or he...

Страница 29: ...hly if the unit is in a coastal or corrosive environment Annual Maintenance Check and tighten all set screws bolts locking collars and sheaves 1 Inspect clean and tighten all electrical connections 2...

Страница 30: ...quired Remedy 1 Check power supply for voltage outside the acceptable voltage range 2 Check the control unit for loose wires Firm any loose connections 3 Replace 4 Check for loose wire connection brok...

Страница 31: ...t run Possible cause 1 Faulty switch 2 Open fan motor coil circuit 3 Fan binding on shroud or venturi ring Remedy 1 Correct as follows a clean b defrost using fan operation only c clean or replace fil...

Страница 32: ...32 PKG SVX14A EN typical wiring diagram Maintenance...

Страница 33: ...PKG SVX01A EN 33 typical wiring diagram Maintenance...

Страница 34: ...34 PKG SVX14A EN typical wiring diagram Maintenance...

Страница 35: ...PKG SVX01A EN 35 typical wiring diagram Maintenance...

Страница 36: ...e mail us at comfort trane com Literature Order Number Date Supersedes Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications...

Отзывы: