PKG-SVX14A-EN
9
Installation
pre-installation
considerations
Table I-PC-1. Isolator load points, units with a vertical discharge configuration, lbs.
model
L1
L2
L3
L4
L1
L2
L3
L4
SCRB/SIRB
SCWB/SIWB
3-ton
99
105
120
127
105
133
118
124
5-ton
115
122
157
166
129
165
166
165
7.5-ton
154
203
227
221
177
234
230
231
10-ton
208
266
273
253
263
334
293
300
15-ton
243
332
359
356
315
388
382
375
Table I-PC-2. Isolator load points, units with a horizontal discharge configuration, lbs.
model
L1
L2
L3
L4
L1
L2
L3
L4
SCRB/SIRB
SCWB/SIWB
7.5-ton
250
108
313
135
285
126
319
140
10-ton
318
150
363
169
383
211
383
211
15-ton
404
166
510
210
514
215
514
215
Table I-PC-3. Isolator load points & types, units with a horizontal discharge, inverted “L”
configuration, lbs.
air-cooled models
water-cooled models
L1
L2
L3
L4
L1
L2
L3
L4
10-ton unit
318
150
363
169
383
211
383
211
spring
red
yellow
red
yellow
red
yellow
red
yellow
rubber-in-shear
green
red
green
red
green
red
green
red
15-ton unit
404
166
510
210
514
215
514
215
spring
purple
yellow
purple
yellow
purple
yellow
purple
yellow
rubber-in-shear
gray
red
gray
red
gray
red
gray
red
Note: Units ship with two different color isolators and should be placed as depicted in this chart to properly support the
unit weight. See Figures I-PC-1 & I-PC-2 for correct isolator positions by unit size.
3, 5, & 7.5-ton units
bottom view of unit
1
7
/
8
1
7
/
8
7
/
8
” dia. hole under all 4 corners
Figure I-PC-1. Isolator mounting hole locations on 3, 5, &
7.5-ton units
10 & 15-ton units
bottom view of unit
1
3
/
8
3
3
/
4
9
/
16
” dia. hole under all 4 corners
Figure I-PC-2. Isolator mounting hole locations on 10 & 15-
ton units
L1
L3
L2
L4
L1
L3
L2
L4
Isolator Placement
Note: Isolators are field-provided.