RLC-SVX19A-E4
9
General Data
RTAF Standard Effi ciency - eXtra Low Noise
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
090
105
125
145
155
175
190
205
Eurovent Performances
SE XLN
SE XLN
SE XLN
SE XLN
SE XLN
SE XLN
SE XLN
SE XLN
Net Cooling Capacity (3) (4)
(kW)
326
376
440
522
564
616
676
732
Power Input (5)
(kW)
101
119
143
162
181
203
217
240
EER (3) (4) (6)
(kW/kW)
3.23
3.17
3.08
3.22
3.12
3.03
3.11
3.05
ESEER (6)
(kW/kW)
4.13
4.07
4.06
4.12
4.02
4.08
4.04
4.01
Eurovent Effi ciency class Cooling
A
A
B
A
A
B
A
B
Sound power level (eXtra Low Noise) (10)
(dBA)
88
89
89
89
90
90
91
91
Middle East design condition performances (7)
Gross cooling capacity
(tons)
77
88
103
124
133
145
160
172
Gross EER
(kW/ton)
1.5
1.5
1.6
1.5
1.5
1.6
1.5
1.6
MEW (Kuwait) rating point performances (8)
Gross cooling capacity
(tons)
73
84
97
117
125
135
150
162
Gross EER
(kW/ton)
1.6
1.7
1.7
1.6
1.7
1.7
1.7
1.7
Table 2 – General Data RTAF 090 – 205 Standard Effi ciency - Extra Low Noise
Compressor
Quantity
#
2
2
2
2
2
2
2
2
Nominal Size (1)
tons
45/45
50/50
70/50
70/70
85/70
100/70
100/85
100/100
Evaporator
Evaporator Model
115B
115A
165B
165B
165A
200B
200B
250C
Water Storage
l
51
58
74
74
78
99
99
109
Two pass Evaporator
Minimum Flow
l/s
8.0
9.4
11.6
11.6
12.4
14.2
14.2
16.2
Maximum Flow
l/s
29.6
34.7
43.1
43.1
46.0
52.6
52.6
60.3
Two pass Evaporator – with Turbulators
Minimum Flow
l/s
6.6
7.8
9.7
9.7
10.3
11.8
11.8
13.5
Maximum Flow
l/s
26.6
31.2
38.7
38.7
41.3
47.2
47.2
54.1
Condenser
Quantity of Coils
#
4/4
4/4
4/4
5/5
5/5
6/4
6/6
6/6
Coil Length
mm
1967
1967
1967
1967
1967
1967
1967
1967
Coil Height
mm
1214
1214
1214
1214
1214
1214
1214
1214
Condenser Fans
Quantity (1)
#
4/4
4/4
4/4
5/5
5/5
6/4
6/6
6/6
Diameter
mm
800
800
800
800
800
800
800
800
Total Air Flow
m
3
/s
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
Nominal RPM
rpm
860
860
860
860
860
860
860
860
Motor
kW
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
Minimum Starting/Operating Ambient
Standard Unit
°C
-10
-10
-10
-10
-10
-10
-10
-10
Low-Ambient Unit (Option)
°C
-20
-20
-20
-20
-20
-20
-20
-20
Maximum ambient operation
Standard ambient (9)
°C
46
46
46
46
46
46
46
46
Maximum ambient operation
High ambient (9)
°C
55
55
55
55
55
55
55
55
General Unit
Refrigerant
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
Number of Independent
Refrigerant Circuits
#
2
2
2
2
2
2
2
2
Minimum Load (2)
%
15
15
15
15
15
15
15
15
Operating Weight
kg
3375
3395
3575
4090
4360
4505
5000
5115
Shipping Weight
kg
3316
3327
3489
4004
4270
4390
4885
4988
R134a refrigerant charge
Circuit1/Circuit 2
(kg)
38/38
36/36
40/39
44/43
47/42
57/48
58/55
66/63
Oil charge Circuit1/Circuit 2
(l)
6/6
6/6
6/6
6/6
7/6
7/6
7/7
8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.