RLC-SVX19A-E4
39
General Electrical Recommendations
Table 19
–
Fan Motor and Control circuit data - Extra Effi ciency
Fan (Each)
Control
Evaporator
Unit Size
Qty
kW (1)/kW (2)
FLA (3)
kW
A
Heater
kW
Standard noise level/Low noise level
090
10
2.56/2.56
3.9
1.776
4.41
0.8
105
10
2.56/2.56
3.9
1.776
4.41
0.8
125
10
2.56/2.56
3.9
1.776
4.41
0.8
145
12
2.56/2.56
3.9
1.776
4.41
0.8
155
12
2.56/2.56
3.9
1.776
4.41
0.8
175
12
2.56/2.56
3.9
1.776
4.41
1.2
190
14
2.56/2.56
3.9
1.776
4.41
1.2
205
14
2.56/2.56
3.9
1.776
4.41
1.2
Extra low noise level
090
10
2.56/2.56
3.9
1.776
4.41
0.8
105
10
2.56/2.56
3.9
1.776
4.41
0.8
125
10
2.56/2.56
3.9
1.776
4.41
0.8
145
12
2.56/2.56
3.9
1.776
4.41
0.8
155
12
2.56/2.56
3.9
1.776
4.41
0.8
175
12
2.56/2.56
3.9
1.776
4.41
1.2
190
14
2.56/2.56
3.9
1.776
4.41
1.2
205
14
2.56/2.56
3.9
1.776
4.41
1.2
Notes:
1. Max power input per Fan for standard & high ambient
2. Max power input per Fan for low ambient
3. Maximum FLA per Fan for standard & high ambient and low ambient
4. Compressor maximum Amps under 400/3/50Hz
5. Compressor Start up Amps under 400/3/50Hz
Table 20
–
Fan Motor and Control circuit data - High Seasonal Effi ciency
Fan (Each)
Control
Evaporator
Unit Size
Qty
kW (1)/kW (2)
FLA (3)
kW
A
Heater
kW
Standard noise level/Low noise level
090
10
2.56/2.56
3.9
1.776
4.41
0.8
105
10
2.56/2.56
3.9
1.776
4.41
0.8
125
10
2.56/2.56
3.9
1.776
4.41
0.8
145
12
2.56/2.56
3.9
1.776
4.41
0.8
155
12
2.56/2.56
3.9
1.776
4.41
0.8
175
12
2.56/2.56
3.9
1.776
4.41
1.2
190
14
2.56/2.56
3.9
1.776
4.41
1.2
205
14
2.56/2.56
3.9
1.776
4.41
1.2
Extra low noise level
090
10
2.56/2.56
3.9
1.776
4.41
0.8
105
10
2.56/2.56
3.9
1.776
4.41
0.8
125
10
2.56/2.56
3.9
1.776
4.41
0.8
145
12
2.56/2.56
3.9
1.776
4.41
0.8
155
12
2.56/2.56
3.9
1.776
4.41
0.8
175
12
2.56/2.56
3.9
1.776
4.41
1.2
190
14
2.56/2.56
3.9
1.776
4.41
1.2
205
14
2.56/2.56
3.9
1.776
4.41
1.2
Notes:
1. Max power input per Fan for standard & high ambient
2. Max power input per Fan for low ambient
3. Maximum FLA per Fan for standard & high ambient and low ambient
4. Compressor maximum Amps under 400/3/50Hz
5. Compressor Start up Amps under 400/3/50Hz