RLC-SVX19A-E4
40
General Electrical Recommendations
Table 21
–
Electrical data
Compressor Data
Control Circuit Data
RTAF
Quantity
Maximum Amps (4)
Starting Amps (5)
Disconnect switch Option
Power Cable Cross section
Size
Cmpr 1
Cmpr 2
Cmpr 1
Cmpr 2
Min (mm²)
Max (mm²)
Standard Effi ciency
90
2
97
97
144
144
185
240
105
2
116
116
180
180
185
240
125
2
158
116
259
180
240
240
145
2
158
158
259
259
2x150
2x300
155
2
197
158
291
259
2x150
2x300
175
2
234
158
354
259
2x185
2x300
190
2
234
197
354
291
2x185
2x300
205
2
234
234
354
354
2x185
2x300
High Effi ciency
90
2
97
97
144
144
185
240
105
2
116
116
180
180
185
240
125
2
158
116
259
180
240
240
145
2
158
158
259
259
2x150
2x300
155
2
197
158
291
259
2x150
2x300
175
2
234
158
354
259
2x185
2x300
190
2
234
197
354
291
2x185
2x300
205
2
234
234
354
354
2x185
2x300
Notes:
1. Max power input per Fan for standard & high ambient
2. Max power input per Fan for low ambient
3. Maximum FLA per Fan for standard & high ambient and low ambient
4. Compressor maximum Amps under 400/3/50Hz
5. Compressor Start up Amps under 400/3/50Hz
Table 22
–
Electrical data
Compressor Data
Control Circuit Data
RTAF
Quantity
Maximum Amps (4)
Starting Amps (5)
Disconnect switch Option
Power Cable Cross section
Size
Cmpr 1
Cmpr 2
Cmpr 1
Cmpr 2
Min (mm²)
Max (mm²)
Extra Effi ciency
90
2
97
97
144
144
185
240
105
2
116
116
180
180
185
240
125
2
158
116
259
180
240
240
145
2
158
158
259
259
2x150
2x300
155
2
197
158
291
259
2x150
2x300
175
2
234
158
354
259
2x185
2x300
190
2
234
197
354
291
2x185
2x300
205
2
234
234
354
354
2x185
2x300
High Seasonal Effi ciency
90
2
90
90
90
90
185
240
105
2
105
105
105
105
185
240
125
2
147
105
147
105
240
240
145
2
147
147
147
147
2x150
2x300
155
2
182
147
182
147
2x150
2x300
175
2
206
147
206
147
2x185
2x300
190
2
206
182
206
182
2x185
2x300
205
2
206
206
206
206
2x185
2x300
Notes:
1. Max power input per Fan for standard & high ambient
2. Max power input per Fan for low ambient
3. Maximum FLA per Fan for standard & high ambient and low ambient
4. Compressor maximum Amps under 400/3/50Hz
5. Compressor Start up Amps under 400/3/50Hz