RLC-SVX19A-E4
15
RTAF Operating Map
To choose the unit confi guration, refer to operating map
fi gure below: Standard ambient, High ambient or Low
ambient.
* Standard ambient units:
-10°C
Air temperature
46°C
* Low ambient units:
-18°C
Air temperature
46°C
* High ambient units:
-10°C
Air temperature
55°C
Note: It is not possible to have a unit operate low and
high ambient.
Figure 16 – RTAF Operating Map
Operating Map
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
-16
-12
-8
-4
0
4
8
12
16
20
24
Entering A
ir
Te
mp
[C]
Leaving Water Temp [C]
Standard ambient
Low ambient
High ambient
Part load