![Trane RTAD 085 Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/trane/rtad-085/rtad-085_installation-operation-and-maintenance_1149696079.webp)
RTAD-SVX01F-E4
79
Maintenance Procedures
Table 40 - Refrigerant Charge
per Circuit (kg).
Unit Size
Circuit A
Circuit B
Standard
Free Cooling
RTAD 085
24
24
RTAD 100
30
32
RTAD 115
35
36
RTAD 125
36
37
RTAD 145
44
48
RTAD 150
44
48
RTAD 165
61
59
RTAD 180
61
61
RTAD 085 HE
32
34
RTAD 100 HE
35
36
RTAD 115 HE
42
45
RTAD 125 HE
42
45
RTAD 145 HE
59
61
RTAD 150 HE
59
61
Partial Heat Recovery
RTAD 085
26
26
RTAD 100
33
35
RTAD 115
38
39
RTAD 125
39
40
RTAD 145
47
51
RTAD 150
47
51
RTAD 165
65
63
RTAD 180
65
65
RTAD 085 HE
35
37
RTAD 100 HE
38
39
RTAD 115 HE
45
48
RTAD 125 HE
45
48
RTAD 145 HE
63
65
RTAD 150 HE
63
65
Total Heat Recovery
RTAD 100
55
52
RTAD 115
67
64
RTAD 125
68
64
RTAD 145
86
84
RTAD 150
86
84
RTAD 165
100
95
RTAD 180
100
98
RTAD 085 HE
63
60
RTAD 100 HE
65
62
RTAD 115 HE
86
84
RTAD 125 HE
86
84
RTAD 145 HE
97
95
RTAD 150 HE
97
95
Note: Size 085 does not exist for Total Heat Recovery
option but HE version is available
Refrigerant Filter Changing
Procedure
A dirty filter is indicated by a
temperature gradient across the
filter, corresponding to a pressure
drop. If the temperature downstream
of the filter is 4.4°C (8°F) lower than
the upstream temperature, the filter
should be replaced. A temperature
drop can also indicate that the unit is
undercharged. Ensure proper
subcooling before taking
temperature readings.
1 With the unit off, verify that the
EXV is closed. Close liquid line
isolation valve. On units with
remote evaporators or oil cooling
circuits, close ball valve on oil
cooler liquid line.
2 Attach vacuum hose to service
port on liquid line filter flange.
3 Evacuate refrigerant from liquid
line and store.
4 Remove vacuum hose.
5 Depress schrader valve to
equalize pressure in liquid line
with atmospheric pressure.
6 Remove bolts that retain filter
flange.
7 Remove old filter element.
8 Inspect replacement filter element
and lubricate o-ring with Trane
OIL00048.
Note: do not use mineral oil. It will
contaminate the system.
9 Install new filter element in filter
housing.
10 Inspect flange gasket and replace
if damaged.
11 Install flange and torque bolts to
19-22 mN (14-16 lb-ft).
12 Attach vacuum hose and
evacuate liquid line.
13 Remove vacuum hose from liquid
line and attach charging hose.
14 Replace stored charge in liquid
line.
15 Remove charging hose.
16 Open liquid line isolation valve.
On units with remote evaporators
or oil cooler circuits, open oil
cooler liquid line ball valve.
Adding Refrigerant
If the entire charge has been
removed, perform the following
procedures to recharge the unit.
1 Open all service valves
2 Establish water flow through the
evaporator. Connect a hose from
the refrigerant bottle to the
backseat port on the liquid line
shutoff valve. Midseat the valve.
CAUTION! The evaporator water
flow needs to be established and
maintained while adjusting the
charge to avoid freezing and
rupturing the tubes.
3 It may not be possible to put the
entire amount of refrigerant charge
required using step 2. If so, start
the unit and add liquid refrigerant
through the liquid line service
valve.
4 Once the unit has been charged
with refrigerant, start the unit.
Measure the subcooling and verify
that the refrigerant charge is
correct.